Plan Review Notes For Permit 13120731 |
Permit Number |
13120731 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-01-27 10:09:05 | PASS PROVISO | | 1) THE EXHAUST SYSTEM MUST BE DESIGNED TO OPERATE WITH | | A STATIC FLUE PRESSURE | | BETWEEN NEGATIVE .15 IN. WG AND POSITIVE 0.25 IN. WG. | | AT THE EXHAUST OF THE | | ROASTER WHILE IN OPERATION. PROVIDE EQUIPMENT TO TEST | | WG AT FINAL INSPECTION. | | 2) SEPARATE PERMIT REQUIRED FOR PLUMBING (GAS LINE) | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|