Plan Review Notes
Plan Review Notes For Permit 13120731
Permit Number 13120731
Review Stop M
Sequence Number 1
Notes
Date Text
2013-12-26 11:37:01PLAN DENIED
 1) PROVIDE THE DUCT LENGTH FROM THE COFFEE ROASTER
 TO THE ROOF.
 2) REFER TO SECTION 506.4.2 TYPE TWO TERMINATION # 4
 3) PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR
 COFFEE ROASTER AND DUCT WRAP WITH THE PLAN.