2014-01-29 13:38:37THE FOLLOWING ITEMS SHALL BE ADDRESSED AND RESUBMIT FOR
 REVIEWS>
 1. NEC 600.05 REQUIRES A SIGN OUTLET BY EVERY ENTRY
 DOOR
 2. NEC 210.62 REQUIRES A SHOW WINDOW LIGHTING OUTLET
 FOR EVERY 12 LINEAR FOOT OF WINDOW.
 3. NEC 110.16 REQUIRES ARC-FLASH WARNING LABELS AT THE
 ELECTRICAL PANELS
 4. NEC 210.08 REQUIRES THAT ALL OUTLETS WITHIN 6' OF
 THE SINK BE GFCI PROTECTED.
 5. MISSING PANEL SCHEDULE AND LOAD CALCS FOR PANEL "B"
 LIGHTING CONDITIONS AS STATED ON THE DRAWINGS DO NOT
 SEEM TO COMPLY WITH THE MINIMUM REQUIREMENTS OF THE
 FBC-ENERGY CONSERVATION CODE SECTION 505
 THE EMERGENCY LIGHTING AS SHOWN ON THE PLANS DO NOT
 COMPLY WITH THE MINIMUM REQUIREMENTS OF NFPA 101
 SECTION 7.9
  
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH BLDG. DEPARTMENT
 (561) 805-6718
  