Plan Review Notes
Plan Review Notes For Permit 13120556
Permit Number 13120556
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2014-02-04 09:45:238100 IBIS BOULEVARD
 PERMIT #13120556
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **CONTRACTOR TO SCHEDULE A #131 FIRE FINAL INSPECTION
 PRIOR TO OCCUPANCY**
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730