2013-12-12 19:09:55 | 2010 FBC / 2008 NEC |
| |
| THE SCOPE OF WORK FOR THIS PROJECT IS TO WIRE AN |
| EXISTING 1434 SQFT RESIDENTIAL STRUCTURE THAT WAS |
| COMPLETELY GUTTED (ALL INTERIOR WALLS WERE REMOVED) |
| THAT WILL HAVE AN ADDITIONAL 112 SQFT ADDED TO IT FOR A |
| TOTAL OF 2546 SQFT. |
| |
| DENIED BY ELECTRICAL |
| |
| 1) PROVIDE TWO SETS OF PLANS WITH A SERVICE RISER |
| DIAGRAM WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING |
| DETAIL. NEC 230, 250 |
| |
| 2) PROVIDE COMPLETE LOAD CALCULATIONS. NEC 220.40 |
| |
| 3) PROVIDE COMPLETE PANEL SCHEDULES. NEC 240 |
| |
| 4) SPECIFY THE METER AND PANEL LOCATIONS ON THE FLOOR |
| PLANS. NEC 230, 408 |
| |
| 5) SPECIFY THE AIC RATING OF THE ELECTRICAL EQUIPMENT. |
| NEC 110.9 |
| |
| 6) LABEL THE ROOMS ON THE ELECTRICAL FLOOR PLANS, |
| SPECIFY THE LOCATIONS OF THE AIR HANDLERS, CONDENSING |
| UNITS, WATER HEATER, WASHER, DRYER, KITCHEN COUNTER |
| TOPS, BATHROOM BASINS, TUBS AND SHOWERS ON THE FLOOR |
| PLAN TO SHOW COMPLIANCE WITH NEC 210.52, 210.63, |
| 406.8(B) |
| |
| 7) SHOW COMPLIANCE WITH NEC 210.8 GFCI, 210.12 AFCI, |
| 406.11 TAMPER-RESISTANT RECEPTACLES WHERE REQUIRED. |
| |
| 8) THESE PLANS SHOW A FIREPLACE THAT IS NOT SHOWN ON |
| THE MASTER PLANS. IF THERE IS A FIREPLACE CARBON |
| MONOXIDE DETECTORS ARE REQUIRED. FBCR 315 |
| |
| 9) IN ADDITION TO THE SIGNATURE, PLEASE PROVIDE THE |
| PRINTED NAME AND LICENSE NUMBER OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN ON THE DRAWINGS. CITY |
| AMENDMENTS 107.2.1 |
| |
| THIS REVIEW IS NOT INTENDED AS A PUNCH LIST TO LIST ALL |
| OF THE DEFICIENCIES WITH THE ELECTRICAL PLANS. DUE TO |
| THE AMOUNT OF MISSING INFORMATION IT IS SUGGESTED THAT |
| THESE PLANS BE REVIEWED BY A LICENSED DESIGN |
| PROFESSIONAL BEFORE THEY ARE RESUBMITTED FOR REVIEW. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| [email protected] |