Plan Review Notes For Permit 13120507 |
Permit Number |
13120507 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2014-05-20 13:27:05 | RESIDENTIAL (R3) GARAGE CONVERSION, THIRD MECHANICAL | | REVIEW CHECKLIST. | | CODE: 2010 FBC. | | | | 1- PROVIDE EQUIPMENT SIZING CALCULATIONS THAT COMPLY | | WITH SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. | | A) NEED TO PROVIDE MANUAL J CALCULATIONS OR ANY OTHER | | APPROVED HEATING AND COOLING CALCULATION METHOD. | | CALCULATIONS SUBMITTED ARE NOT APPROVED BY THE FLORIDA | | BUILDING COMMISSION. CALCULATIONS TO INCLUDE THE | | MANUFACTURER AND MODEL NUMBER WITH THE SENSIBLE AND | | TOTAL COOLING CAPACITIES. EQUIPMENT CAPACITY CAN'T BE | | MORE THAN 1.15 TIMES GREATER THE TOTAL CALCULATED LOAD. | | | | 2- A/C PLAN PROVIDED: | | A) SPECIFY ON THE A/C PLAN THE EQUIPMENT LISTED ON THE | | EQUIPMENT SIZING CALCULATIONS. SEC. 103.2.2 OF 2010 | | FBC-ENERGY CONSERVATION. | | | | B) RETURN AIR GRILLE SHOWN BY THE SITTING ROOM DOESN'T | | SHOW ANY DUCTWORK. CLARIFY HOW IS IT CONNECTED TO THE | | AIR HANDLING UNIT. SEC. 103.2.2 OF 2010 FBC-ENERGY | | CONSERVATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 |
|