2014-05-20 13:27:05RESIDENTIAL (R3) GARAGE CONVERSION, THIRD MECHANICAL
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS THAT COMPLY
 WITH SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
 A) NEED TO PROVIDE MANUAL J CALCULATIONS OR ANY OTHER
 APPROVED HEATING AND COOLING CALCULATION METHOD.
 CALCULATIONS SUBMITTED ARE NOT APPROVED BY THE FLORIDA
 BUILDING COMMISSION. CALCULATIONS TO INCLUDE THE
 MANUFACTURER AND MODEL NUMBER WITH THE SENSIBLE AND
 TOTAL COOLING CAPACITIES. EQUIPMENT CAPACITY CAN'T BE
 MORE THAN 1.15 TIMES GREATER THE TOTAL CALCULATED LOAD.
  
 2- A/C PLAN PROVIDED:
 A) SPECIFY ON THE A/C PLAN THE EQUIPMENT LISTED ON THE
 EQUIPMENT SIZING CALCULATIONS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 B) RETURN AIR GRILLE SHOWN BY THE SITTING ROOM DOESN'T
 SHOW ANY DUCTWORK. CLARIFY HOW IS IT CONNECTED TO THE
 AIR HANDLING UNIT. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER