Plan Review Notes
Plan Review Notes For Permit 13120507
Permit Number 13120507
Review Stop B
Sequence Number 2
Notes
Date Text
2014-03-13 17:04:15RESIDENTIAL (R3) GARAGE CONVERSION, SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- PLANS SUBMITTED NOW ARE MISSING THE ENGINEER'S SEAL.
 CHAPTER 471 FL. ST.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) HURRICANE SHUTTERS FOR WINDOWS THAT DON'T HAVE
 IMPACT GLAZING. (REPEAT COMMENT. NOT ADDRESSED).
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 4- HURRICANE SHUTTERS: PROVIDE COMPLETE INSTALLATION
 SCHEDULE ( SEE CITY SAMPLE OF INSTALLATION SCHEDULE OR
 PROVIDE ANOTHER FORMAT THAT PROVIDES ALL THE
 INFORMATION).
 ***NOTE: CLEARLY IDENTIFY SPECIFIC MOUNTING CONDITIONS
 AND SPECIFIC ANCHOR TYPE AND SPACING TO BE USED. SEC.
 107.2.1 CITY AMENDMENTS. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 5- SHEET A-2:
 A) SHOW COMPLIANCE WITH THE EGRESS REQUIREMENTS FOR THE
 BEDROOM AS REQUIRED BY SEC. R310 OF 2010
 FBC-RESIDENTIAL. (NOTE: SHEET A-1 SHOWS EXISTING
 BEDROOM, THERE ARE NO PERMITS ON CITY RECORDS FOR THE
 CONVERSION). (REPEAT COMMENT. NOT ADDRESSED).
  
 B) PROVIDE COMPLIANCE WITH THE HEATING REQUIREMENTS OF
 SEC. R303.8 OF 2010 FBC-RESIDENTIAL. (REPEAT COMMENT.
 NOT ADDRESSED). FLOOR PLAN ONLY SHOWS AN A/C SHAFT NEXT
 TO THE CLOSET. NO A/C INFORMATION WAS PROVIDED).
  
 C) PROVIDE COMPLETE FRAMING DETAILS FOR THE NEW
 EXTERIOR OPENINGS, INCLUDING THE BEDROOM WINDOW AND NEW
 DOUBLE FRENCH DOORS. SEC. R301.1. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 D) NEW DOUBLE FRENCH DOOR: SPECIFY MASONRY OPENING
 VERTICAL REINFORCEMENT AS REQUIRED BY SEC. R609.3.2.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 E) REVISE EXTERIOR FRENCH DOORS NOTE #2. REVISE THE
 BUILDING EXPOSURE. IT'S EXPOSURE "C" NOT "B". (REPEAT
 COMMENT).
 ***NOTE: SAME COMMENT APPLIES TO WINDOWS NOTES. REVISE
 AS REQUIRED. (REPEAT COMMENT).
  
 F) REVISE ALL WINDOWS AND DOORS NOA NUMBER AND
 MANUFACTURER SPECIFIED ON THE FLOOR PLAN AND WINDOWS
 AND DOORS NOTES TO MATCH ACTUAL PRODUCT APPROVALS
 SUBMITTED FOR REVIEW. SEC. 107.2.1 CITY AMENDMENTS TO
 FBC.
  
 6- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE
 DUE. THEN, BRING BACK COUNTY STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE. (REPEAT COMMENT. NOT ADDRESSED).
  
 7- SCOPE OF WORK IS TO CONVERT GARAGE TO LIVING SPACE,
 NOT TO REPLACE WINDOWS/DOORS AND MOVE BATHROOM
 LOCATION. VALUATION DECLARED IN THE PERMIT APPLICATION
 IS TOO LOW. UPDATE VALUATION TO INCLUDE ALL LABOR,
 MATERIALS, CONTRACTOR'S OVERHEAD/ PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 OF CITY
 AMENDMENTS.
  
 ***NOTES:
 *PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712