Plan Review Notes For Permit 13120507 |
Permit Number |
13120507 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-02-05 09:44:50 | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | FBC- 107.3.5.3 PROVIDE AN ELECTRIC SERVICE RISER WITH | | WIRE SIZES, IF THE PANEL SHOWN IS A SUB PANEL, SHOW HOW | | FED. PROVIDE COMPLETE LOAD CALCULATIONS, PANEL | | SCHEDULES. | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|