Plan Review Notes For Permit 13120505 |
Permit Number |
13120505 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-12-22 13:04:56 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. REVISE PLAN TO INDICATE ROOM DESIGNATION, FBC | | EXISTING BUILDING 604.1. | | | | 2. REVISE FLOOR PLAN TO PROVIDE THE FOLLOWING | | INFORMATION FOR BEDROOMS; FBC R310, FBC EB 604.1. THE | | CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%: | | | | REVISE PLAN TO STATE WHAT TYPE OF WINDOW IS THERE NOW | | IN THE BEDROOMS - AWNING, CASEMENT, SINGLE HUNG? | | | | REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING | | DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH | | EXISTS WHEN THE WINDOW IS FULLY OPEN. | | | | REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING | | DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE | | MANUFACTURER. | | | | 3. SHUTTER CONNECTION MOUNTING TYPE (INSTALLATION | | SCHEDULE) IS TO CORRELATE WITH THE PRODUCT APPROVAL | | ANCHR CHART. FOR EXAMPLE, SEE SHEET 6; CONNECTION TYPES | | ARE NAMED 1(TOP), 1(BOTTOM), 2(TOP), ETC. | | | | | | | | |
|