Date |
Text |
2014-04-25 18:59:24 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) THE PRODUCT APPROVAL FOR THE TRULITE SINGLE HUNG |
| WINDOWS (NOA NO.12-0118.16) EXPIRED IN 2012. SUBMIT A |
| CURRENT PRODUCT APPROVAL THAT HAS BEEN APPROVED BY THE |
| DESIGNER OF RECORD. DCA RULE 9N-3 AND CITY AMENDMENTS |
| 107.3.4.1 |
| |
| 2) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES FROM |
| THE GAF SELF-ADHERING ROOFING SYSTEM (NOA NO. |
| 14-0102.12) WILL BE USED. SPECIFY THE FASTENING OPTION |
| AND MAXIMUM DESIGN PRESSURE FOR THE SYSTEM. SUBMIT TWO |
| SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS FOR |
| ENHANCED FASTENING AT THE CORNER AND PERIMETER AREAS IN |
| ACCORDANCE WITH LIMITATION NUMBER 7 OF THE NOA. FBCR |
| 301.1 |
| |
| 3) CLARIFY WHERE THE MTS 20 STRAPS SPECIFIED ON PAGE 6 |
| ARE TO BE USED. THE WALL SECTION ON PAGE 3 SHOWS A |
| SIMPSON H10 CONNECTOR AT EACH RAFTER. CITY AMENDMENTS |
| 107.2.1 |
| |
| 4) THE FASTENERS THAT ARE SPECIFIED FOR THE MTS 20 |
| STRAPS ARE INCORRECT. TAPCONS ARE NOT APPROVED |
| FASTENERS FOR SIMPSON CONNECTORS. THEY REQUIRE TITAN |
| MASONRY SCREWS. THE MTS 20 REQUIRES (7) 10D X 1-1/2" |
| INTO THE TRUSS AND (7) 10D X 1-1/2" INTO THE WALL PLATE |
| FOR A TOTAL OF 14 FASTENERS FOR WOOD TO WOOD |
| CONNECTIONS. YOU WILL NEED TO PROVIDE DOCUMENTATION |
| FROM SIMPSON IF YOU WISH TO MODIFY THE INTENDED AND |
| TESTED USE OR FASTENERS. FBCR 301.1 AND DCA RULE 9N-3 |
| |
| 5) PLEASE CLARIFY THE ENHANCED NAILING PATTERN FOR |
| ROOFING NOTE ON PAGE 6. IF THIS IS INTENDED FOR THE |
| BASE SHEET ATTACHMENT OF THE GAF SELF-ADHERING ROOFING |
| SYSTEM (NOA NO. 14-0102.12), IT IS NOT ACCEPTABLE. RAS |
| 117 CALCULATIONS ARE REQUIRED FOR THAT AS STATED ABOVE. |
| CITY AMENDMENTS 107.2.1 |
| |
| 6) THE VALUE OF THE WORK ON THE APPLICATION IS |
| $2000.00. THIS IS TOO LOW. INCLUDE THE VALUE OF ALL THE |
| WORK DONE WITHOUT PERMITS, ALL OF THE PROPOSED WORK |
| INCLUDING LABOR, MATERIALS, COST, OVERHEAD AND PROFIT. |
| CITY AMENDMENTS 109.3. |
| |
| 7) IN ORDER TO SPEED THE REVIEW PROCESS, PLEASE SUBMIT |
| A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS WAS ADDRESSED. |
| |