2014-01-16 08:39:14 | 2010 FBC | | | | DENIED BY MECHANICAL | | | | 1) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE | | STRUCTURE WHICH IS TO BEING CONVERTED TO CONDITIONED | | SPACE. THE FORM IS TO BE SIGNED AND DATED BY THE PERSON | | THAT PREPARES IT AND THE OWNER/AGENT. FBC ENERGY | | CONSERVATION 101.4.5 | | | | 2) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS | | IN ACCORDANCE WITH FBC FBCR M1401.3. THE EQUIPMENT THAT | | IS SPECIFIED ON THE PLANS IS REQUIRED TO MATCH THE | | SIZING CALCULATIONS. | | | | 3) REVISE THE PLANS TO SHOW THE CLOTHES DRYER EXHAUSTED | | TO THE OUTSIDE OF THE BUILDING AND AT LEAST 3 FEET FROM | | ANY OPENINGS INTO THE BUILDING. FBCR M1502 | | | | 4) REVISE THE PLANS TO SHOW THE BATHROOM VENTILATION | | EXHAUSTED TO THE OUTSIDE OF THE BUILDING. FBCR M 1507 | | | | 5) THE MECHANICAL PLANS DO NOT SHOW HOW THE AIR WILL BE | | RETURNED TO THE AIR HANDLER. SPECIFY THE SIZE OF THE | | RETURN AIR GRILL OR THAT THE DOOR TO THE A/H CLOSET IS | | A LOUVERED DOOR. FBCR M1602.2 | | | | 6) THE EQUIPMENT SCHEDULE SPECIFIES A TOTAL AIR FLOW OF | | 600 CFMS, BUT THE DUCT LAYOUT ONLY SHOWS 200 CFMS. | | PLEASE CORRECT. CITY AMENDMENTS 107.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|