Date |
Text |
2014-01-16 10:12:18 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| BASED ON THE CITY OF WPB BUILDING DEPARTMENT RECORDS, |
| THIS STRUCTURE WAS A DETACHED GARAGE APPROXIMATELY 13' |
| X 22' IN SIZE. THE APPROXIMATELY 5' X 18' AREA WITH THE |
| BATHROOM AND LAUNDRY ROOM WAS ADDED AT A LATER DATE |
| WITHOUT PERMITS OR INSPECTIONS. |
| |
| 1) THE DESIGN CRITERIA ON SHEET 3 IS INCORRECT. PLEASE |
| UPDATE IT TO MATCH SHEET 1. 2010 FBC R301.2.1 AND ASCE |
| 7-10. |
| |
| 2) ON SHEET 1 THE BUILDING CLASSIFICATION IS SPECIFIED |
| AS III B. IF THIS IS REFERRING TO THE TYPE OF |
| CONSTRUCTION FOR THE STRUCTURE, IT WOULD BE V B PER FBC |
| TABLE 601. |
| |
| 3) THE DESIGN PARAMETERS ON SHEET 3 SPECIFY THE |
| BUILDING DESIGN AS CAVERED. WAS THIS MEANT TO SAY |
| ENCLOSED? PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 |
| |
| 4) PROVIDE A CONNECTOR SCHEDULE THAT SPECIFIES THE TYPE |
| AND NUMBER OF FASTENERS, THE ALLOWABLE LOADS AND THE |
| PRODUCT APPROVAL NUMBERS FOR THE SPECIFIED CONNECTORS |
| ON THE PLANS OR SUBMIT TWO COPIES OF PRODUCT APPROVALS |
| FOR EACH OF THEM. DCA RULE 9N-3 AND FBCR 301.1 |
| |
| 5) SPECIFY THE ROOF SLOPE ON THE PLANS. THE ELEVATIONS |
| ON SHEET 5 OF THE PLANS SHOW THAT THE SAME ROOF SLOPE |
| IS CONTINUED OVER THE BATHROOM AND LAUNDRY AREAS. THE |
| PHOTO OF THE STRUCTURE ON SHEET 1 OF THE PLANS SHOW |
| THAT THE ROOF SLOPE IS LESS OVER THIS AREA. PLEASE |
| CLARIFY. CITY AMENDMENTS 107.2.1 NOTE: THE MINIMUM |
| SLOPE FOR ASPHALT SHINGLES IS 2/12 PER FBCR 905.2.2. |
| |
| 6) INDICATE THE TYPE AND SIZE OF THE WINDOW SHOWN ON |
| THE PLANS AND SUBMIT TWO COPIES OF PRODUCT APPROVALS |
| FOR THE WINDOW. NOTE: BECAUSE THIS IS A STORAGE SHED |
| NOT DESIGNED FOR HUMAN HABITATION AND HAS A FLOOR AREA |
| OF LESS THAN 720 SQFT, LARGE MISSILE IMPACT PROTECTION |
| IS NOT REQUIRED (FBC R301.2.1.2 (2) . |
| |
| 7) SPECIFY ON THE PLANS THAT THIS STRUCTURE IS NOT |
| DESIGNED NOR INTENDED TO BE USED AS HABITABLE SPACE. |
| CITY AMENDMENTS 107.2.1 |
| |
| 8) THE VALUE SPECIFIED ON THE PLANS OF $2000.00 IS TOO |
| LOW. PLEASE PROVIDE A REASONABLE VALUE FOR THIS PROJECT |
| THAT INCLUDES THE UN-PERMITTED ADDITION, THE |
| UN-PERMITTED PLUMBING WORK, THE ELECTRIC WORK, THE NEW |
| HEATING AND AIR SYSTEM, STRUCTURAL AND OTHER SPECIFIED |
| WORK. FOR PERMITTING PURPOSES THE VALUATION IS TO BE |
| THE TOTAL REPLACEMENT COST AND IS REQUIRED TO INCLUDE |
| THE COSTS OF ALL LABOR, MATERIALS, DESIGN COSTS, |
| OVERHEAD AND PROFIT AS WOULD BE CHARGED BY A |
| CONTRACTOR. CITY AMENDMENTS 109.3 |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| [email protected] |