2014-04-09 12:03:55 | BUILDING PLAN REVIEW |
| PERMIT: 13120456 |
| ADD: 424 PALM ST |
| CONT: COMET & ELECTRIC |
| TEL: (561) 689-4400 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: WED. APRIL 09/ 2014 |
| ACTION: DENIED |
| |
| 1-2) COMPLIED. |
| 2) THE SURVEY DOES NOT INDICATE WHERE THE LOCATION OF |
| THE NEW GENERATOR WILL BE LOCATED. 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 3) 2ND REVIEW, TYPICAL GENERATOR PAD DETAILS ARE BY |
| DAVID CARMO P. E.. PLANS ARE COPIED NOT SIGNED NOR |
| SEALED. |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| FL ADMIN CODE 61G15-23.002 ENGINEERS |
| EFFECTIVE DATE 05/06/2009 |
| THE PLANS DO NOT SHOW HOW THE GENERATOR WILL BE |
| ANCHORED TO RESIST, SLIDDING AND THE MOMENT OF |
| OVERTURNING, NOR IS THERE PLANS INCLUDED SHOWING A |
| FOUNDATION/ SLAB AND REINFORCEMENT NOR WIND DESIGN |
| CRITERIA. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED, |
| MWFRS (MAIN WIND FORCE RESISTING SYSTEM FOR MOMENT OF |
| OVERTURNING. |
| |