2013-12-26 09:58:13 | BUILDING PLAN REVIEW |
| PERMIT: 13120456 |
| ADD: 424 PALM ST |
| CONT: COMET & ELECTRIC |
| TEL: (561) 689-4400 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURSDAY DEC. 26/2013 |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION INDICATES THE GENERATOR |
| PROVIDED BY OTHERS, THE COST OF THE GENERATOR IS TO BE |
| APPLIED TO THE JOB VALUE EVEN WHEN IT IS BOUGHT BY THE |
| OWNERS, IT IS PART OF THE SCOPE OF WORK TO BE |
| COMPLETED. VALUE IS LOW. |
| W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| APPLICABLE GOVERNING AUTHORITY. |
| |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 2) THE SURVEY DOES NOT INDICATE WHERE THE LOCATION OF |
| THE NEW GENERATOR WILL BE LOCATED. 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 3) THE PLANS DO NOT SHOW HOW THE GENERATOR WILL BE |
| ANCHORED TO RESIST, SLIDDING AND THE MOMENT OF |
| OVERTURNING, NOR IS THERE PLANS INCLUDED SHOWING A |
| FOUNDATION/ SLAB AND REINFORCEMENT NOR WIND DESIGN |
| CRITERIA. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED, |
| MWFRS (MAIN WIND FORCE RESISTING SYSTEM FOR MOMENT OF |
| OVERTURNING. |
| |