Plan Review Notes For Permit 13120383 |
Permit Number |
13120383 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-12-19 13:57:42 | FBC 2010 EXISTING BUILDING CODE | | FBC 2010 ACCESSIBILITY CODE | | FBC 2010 PLUMBING REVIEW #1 | | DENIED: | | | | 1. A HI/LOW DRINKING FOUNTAIN WILL BE REQUIRED PER FBC | | ACCESSIBILITY | | 211.2 MINIMUM NUMBER. | | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. | | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH | | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH | | 602.7. | | | | 2. THERE WILL NOT BE ENOUGH SPACE INSIDE AND ENOUGH | | CLEAR SPACE IN FRONT OF THE H/C SHOWER. | | 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS. | | TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES | | (915 MM) BY 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS | | MEASURED AT THE CENTER POINTS OF OPPOSING SIDES AND | | SHALL HAVE A 36 INCH (915 MM) WIDE MINIMUM ENTRY ON THE | | FACE OF THE SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES | | (915 MM) WIDE MINIMUM BY 48 INCHES (1220 MM) LONG | | MINIMUM MEASURED FROM THE CONTROL WALL SHALL BE | | PROVIDED. | | | | 3. THE LAVITORY IS REQUIRED TO BE OUTSIDE OF THE 60" | | CLEAR SPACE FOR THE WATER CLOSET. | | 604.3.1 SIZE. | | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES | | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE | | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED | | PERPENDICULAR FROM THE REAR WALL. | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|