Plan Review Notes
Plan Review Notes For Permit 13120383
Permit Number 13120383
Review Stop E
Sequence Number 1
Notes
Date Text
2014-01-13 16:55:48PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE PLAN INDICATES PANEL LP3A LOCATED IN SUITE 302
 CONTROLS ELECTRICAL CUIRCUITS LOCATED IN SUITE 300 AND
 IN THE COMMON CORRIDOR UTILIZED FOR EGRESS.
 PER NEC 240.24 (A) & (B) PANELS SHALL BE LOCATED SUCH
 THAT OVER CURRENT DEVICES ARE ACCESSIBLE AND THAT
 OCCUPANTS SHALL HAVE ACCESS TO OCP DEVICES.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  