Plan Review Notes
Plan Review Notes For Permit 13120373
Permit Number 13120373
Review Stop B
Sequence Number 2
Notes
Date Text
2014-01-25 09:55:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FROM PREVIOUS LIST:
  
 1. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA
 FBC1603.1.4.
  
 SOMEONE ADDED A HANDWRITTEN NOTE "CHAPTER 1603.1.4" TO
 THE LOCATION PLAN. THIS DOES NOT ADDRESS THE COMMENT.
 ENGINEER IS TO REVISE THE PLAN TO INCLUDE THE WIND
 DESIGN CRITERIA (INCORPORATE INTO THE PLAN), REPRINT,
 AND RE-SEAL AS IT IS NOT POSSIBLE TO DETERMINE WHO HAS
 MADE THE CHANGE. IF THE ENGINEER MADE THE CHANGE,
 PLEASE HAVE THE ENGINEER EXPLAIN WHY HE HAS QUOTED A
 CODE SECTION RATHER THAN PROVIDE THE REQUIRED
 INFORMATION.
  
 NEW COMMENTS:
  
 2. SEE FAC61G15-23.002 REGARDING TITLE BLOCK
 REQUIREMENTS FOR THE ENGINEER. REVISE PLANS
 ACCORDINGLY.
  
 3. AS ENGINEER'S RECEIPT OF FIRST COMMENT LIST IS NOT
 CLEAR, PROVIDE A RESPONSE LETTER FROM THE ENGINEER
 STATING HOW THE COMMENTS WERE ADDRESSED. ENGINEER HAS
 RE-SIGNED AND SEALED ONE SHEET WITH A NEW DATE, BUT IT
 IS NOT CLEAR WHO ALTERED THE ENGINEER'S PLAN. IF IT WAS
 SOMEONE OTHER THAN THE ENGINEER, PLEASE NOTE THAT ONLY
 THE ENGINEER CAN ALTER THE SIGNED AND SEALED PLAN. SEE
 ITEM 1.
  