Plan Review Notes For Permit 13120357 |
Permit Number |
13120357 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-02-04 19:10:16 | THIS APPLICATION FAILED THE ELECTRICAL REVIEW AND THE | | FOLLOWING CORRECTIONS SHALL BE MADE. | | 1.TABLE 310.15(B) OF THE NEC NO LONGER APPLIES TO THE | | SERVICE AS THE NEW OCCUPANCY IS A BUSINESS. | | 2. EMERGENCY LIGHTING AS PER FBC, LIFE SAFETY & NFPA | | SHALL BE PROVIDED. | | 3. EXIT LIGHTING COMP[LYING WITH THE ABOVE CODES SHALL | | ALSO BE PROVIDED. | | 4. THE SIGN OUTLET REQUIRED BY NEC 600.5 SHALL BE | | PROVIDED, AS WELL AS SHOW WINDOW LIGHTING IF | | APPLICABLE. | | 5. INCLUDE IN THE RISER DIAGRAM THE INTER-SYSTEM | | BONDING TERMINAL REQUIRED BY NEC 250.94 | | 6. AS PER NEC 422.52, THE WATER COOLER SHALL BE ON A | | GFI PROTECTED CIRCUIT. | | 7. SHOW WITH MORE DETAIL THE PROPOSED ELECTRIC FOR THE | | HVAC SYSTEM, INCLUDING THE REQUIRED DISCONNECTS. | | 8. YOUR LIGHTING SHALL COMPLY WITH ALL THE REQUIREMENTS | | OF THE FBC-ENERGY CONSERVATION CODE. | | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | CONTACT: | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | CITY OF WEST PALM BEACH BLDG. DEPARTMENT | | PH: (561) 805-6718 | | |
|