2014-01-02 17:34:46 | BUILDING PLAN REVIEW |
| PERMIT: 13120304 |
| ADD: 2627 OKEECHOBEE BLVD STORE 102 |
| CONT: TO BE DETERMINED |
| TEL: (954)748-7420 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURSDAY JAN. 02/2014 |
| ACTION: DENIED |
| |
| 1) 2010 FL EXISTING BUILDING CODE THE DESIGNER OF |
| RECORD HAS NOT INDICATED AS TO WHICH METHOD COMPLIANCE |
| WITH SECTION: |
| 101.5 COMPLIANCE METHODS. |
| THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION |
| OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY |
| WITH ONE OF THE METHODS LISTED IN SECTIONS 101.5.1 |
| THROUGH 101.5.3 AS SELECTED BY THE APPLICANT. |
| APPLICATION OF A METHOD SHALL BE THE SOLE BASIS FOR |
| ASSESSING THE COMPLIANCE OF WORK PERFORMED UNDER A |
| SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE CODE |
| OFFICIAL. SECTIONS 101.5.1 THROUGH 101.5.3 SHALL NOT BE |
| APPLIED IN COMBINATION WITH EACH OTHER. |
| |
| 2) IN THE AREA WORK METHOD LEVEL 1 OR LEVEL 2 REQUIRES |
| COMPLIANCE WITH THE FL ACCESSIBILITY CODE, |
| LEVEL 1, 605.1 GENERAL. ACCESSIBILITY SHALL BE IN |
| ACCORDANCE WITH THE PROVISIONS OF THE FLORIDA BUILDING |
| CODE, ACCESSIBILITY. |
| LEVEL 2, 706.1 GENERAL. A BUILDING, FACILITY, OR |
| ELEMENT THAT IS ALTERED SHALL COMPLY WITH THE |
| PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY. |
| |
| NOTE THE RESTROOMS ARE NOT ONLY GETTING NEW FINISHES |
| BUT THE STALLS ARE BEING RECONFIGURED(PERMIT # |
| 03120529) SHOWS A DIFFERENT CONFIGURATION THAN WHAT |
| SHOWS ON THIS PERMIT. 2010 EXISTING BUILDING CODE LEVEL |
| II 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, |
| COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2A) PLEASE PROVIDE ACCESSIBLE RESTROOMS THAT WIL MEET |
| THE REQUIREMENTS OF 2010 FBC-ACCESSIBILITY CODE 604.3.2 |
| OVERLAP. |
| THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE |
| PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB |
| BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT |
| HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE |
| AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE |
| TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL |
| BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE. |
| |
| 2B) THE DOORS THAT FORM THE RESTROOM VESTIBULE DO NOT |
| MEET THE 2010 FL ACCESSIBILITY CODE SEE DOORS IN |
| SERIES. 404.2.6 DOORS IN SERIES AND GATES IN SERIES. |
| THE DISTANCE BETWEEN TWO HINGED OR PIVOTED DOORS IN |
| SERIES AND GATES IN SERIES SHALL BE 48 INCHES (1220 MM) |
| MINIMUM PLUS THE WIDTH OF DOORS OR GATES SWINGING INTO |
| THE SPACE. |
| |
| 3) THE ASSOCIATES LOUNGE IS LOCATED IN ROOM 107 WHICH |
| IS LOCATED ON A MEZZININE LEVEL UNDER PERMIT (0312-529) |
| THERE APPEARS TO BE A HANDICAPPED LOUNGE ON THE FLOOR |
| LEVEL WHERE YOU DID NOT HAVE TO GO THROUGH THE |
| STOCKROOM, NOW IN THE PROPOSED LAYOUT AN ASSOCIATE THAT |
| IS DISABLED WOULD HAVE TO TRAVEL THROUGH THE STOCKROOM |
| TO GET TO THE ACCESSIBLE LOUNGE. ALTERATIONS ARE NOT |
| SUPPOSE TO MAKE THE ACCESSWIBLE ROUTE LESS ACCESSABLE. |
| |
| 4) SHEET A102 DETAIL # 6 INDICATES THE USE OF A NEW |
| PREFABRICATED STAIR, GAURDRAIL & HANDRAIL SYSTEM, |
| PLEASE PROVIDE LIVE LOADS FOR THE STAIR DESIGN PER 2010 |
| FBC-B TABLE 1607.1 AND A PROFILE OF THE GAURDRAIL |
| HANDRAIL SYSTEM SHOWING COMPLIANCE WITH 1013 SINCE THIS |
| IS PART OF THE EXIT DISCHARGE. |
| |
| JAMES A. WITMER CBO |