Plan Review Notes For Permit 13120279 |
Permit Number |
13120279 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-02-04 14:17:49 | NOW THAT LEGIBLE DRAWINGS HAVE BEEN PROVIDED A REVIEW | | HAS BEEN COMPLETED. THE FOLLOWING CORRECTIONS ARE | | REQUIRED: | | 1.THE VERTICAL CLEARANCE FOR THE SERVICE SHALL COMPLY | | WITH ALL THE REQUIREMENTS OF NEC 230.24 | | 2. THOUGH INCLUDED IN THE LOAD CALCS OF THE PANEL, THE | | REQUIRED SHOW WINDOW OUTLETS ARE NOT REFLECTED ON THE | | DRAWINGS. FURTHERMORE, THE OUTLET REQUIRED BY NEC 600.5 | | SHALL BE INCLUDED AS WELL. | | 3. AS PER NEC 210.8, ALL OUTLETS IN THE KITCHEN AREA | | SHALL BE GFI PROTECTED. | | 4. SERVICE GROUNDING SHALL BE IN ACCORDANCE WITH | | ARTICLE 250 OF THE NEC | | 5. AS PER THE FBC AND NFPA, EMERGENCY LIGHTING IS | | REQUIRED IN THE BATHROOMS. | | 6. A PROPER LIGHTING SCHEDULE AND DIAGRAM MEETING THE | | REQUIREMENTS OF FBC-ENERGY CONSERVATION SHALL BE | | PROVIDED. | | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | CONTACT: | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | CITY OF WEST PALM BEACH BLDG. DEPARTMENT | | PH: (561) 805-6718 | | |
|