Plan Review Notes For Permit 13120217 |
Permit Number |
13120217 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-12-06 07:13:17 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. THE ASSEMBLY SELECTED REFERS TO GENERAL LIMITATION | | #9. SEE LAST PAGE OF NOA, ENHANCED FASTENING NOT | | PERMITTED; ASSEMBLY IS TO EITHER MEET REQUIRED DESIGN | | PRESSURES OR REFER TO GENERAL LIMITATION #7. | | | | 2. CALCULATIONS ARE TO BE IN ACCORDANCE WITH | | FAC61G15-23. EITHER AN INDEX SHEET TO BE INCLUDED OR | | EACH SHEET SIGNED AND SEALED. TITLE BLOCK TO INCLUDE | | CERTIFICATE OF AUTHORIZATION NUMBER. | | |
|