Notes
Date Text
2013-12-18 16:28:27REVIEW BY J SAEZ, PX 1328
  
 PASSED W/PROVISOS
  
 1. V1.34 LATERAL DUCT (NO TIE IN TO MAIN DUCTWORK
 ELBOW), SHEET M1
 2. NO PVC ABOVE THE RETURN AIR PLENUM
 3. PROVIDE FLOAT SWITCH ON AHU
  
  