2013-12-27 08:40:55BUILDING PROVISO:
 CORRECTED TERMINOLOGY FROM SERVICE CORRIDOR TO EXIT
 PASSAGEWAY. EXIT PASSAGEWAYS REQUIRE 1 HOUR FIRE RATED
 CONSTRUCTION (FBC-B 1023.3) WITH 1 HOUR OPENING
 PROTECTION AT DOORWAYS (TABLE 715.4.).
  
 JAMES A. WITMER CBO