2013-12-27 08:40:55 | BUILDING PROVISO: | | CORRECTED TERMINOLOGY FROM SERVICE CORRIDOR TO EXIT | | PASSAGEWAY. EXIT PASSAGEWAYS REQUIRE 1 HOUR FIRE RATED | | CONSTRUCTION (FBC-B 1023.3) WITH 1 HOUR OPENING | | PROTECTION AT DOORWAYS (TABLE 715.4.). | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] |
|