Plan Review Notes
Plan Review Notes For Permit 13120143
Permit Number 13120143
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-12-19 11:26:27501 SOUTH FLAGLER DRIVE - #301
 PERMIT #13120143
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A-1.0: BOTH EXISTING STAIR TOWERS ARE OPEN TO THE
 SAME COMMON AREA (ELEVATOR "LOBBY") WHICH MAY RESULT IN
 BOTH STAIRS BEING COMPROMISED BY A SINGLE EVENT. PER
 NFPA 101 SECTION 7.5.1.3.5 IN EXISTING BUILDINGS, WHERE
 MORE THAN ONE EXIT, EXIT ACCESS, OR EXIT DISCHARGE IS
 REQUIRED, SUCH EXITS, EXIT ACCESSES, OR EXIT DISCHARGES
 SHALL BE EXEMPT FROM THE DIAGONAL MEASUREMENT
 SEPARATION DISTANCE CRITERIA OF 7.5.1.3.2 AND
 7.5.1.3.3, PROVIDED THAT SUCH EXITS, EXIT ACCESSES, OR
 EXIT DISCHARGES ARE REMOTELY LOCATED IN ACCORDANCE WITH
 7.5.1.3.1. PER NFPA 101 SECTION 7.5.1.3.1 WHERE MORE
 THAN ONE EXIT, EXIT ACCESS, OR EXIT DISCHARGE IS
 REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH
 EXITS, EXIT ACCESSES, OR EXIT DISCHARGES SHALL BE
 REMOTELY LOCATED FROM EACH OTHER AND BE ARRANGED TO
 MINIMIZE THE POSSIBILITY THAT MORE THAN ONE HAS THE
 POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER
 EMERGENCY CONDITION.
  
 SHEET FA1.1: PROVIDE A FIRE ALARM NOTIFICATION
 APPLIANCE IN THE LARGE STORAGE ROOM (#103).
  
 FIRE SPRINKLER: FOR ISSUANCE OF A GENERAL BUILDING
 PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING
 CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION
 DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE
 AUTOMATIC FIRE SPRINKLERS. AFTER THE BUILDING PERMIT
 HAS BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT
 SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  