2013-12-19 11:26:27 | 501 SOUTH FLAGLER DRIVE - #301 |
| PERMIT #13120143 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| SHEET A-1.0: BOTH EXISTING STAIR TOWERS ARE OPEN TO THE |
| SAME COMMON AREA (ELEVATOR "LOBBY") WHICH MAY RESULT IN |
| BOTH STAIRS BEING COMPROMISED BY A SINGLE EVENT. PER |
| NFPA 101 SECTION 7.5.1.3.5 IN EXISTING BUILDINGS, WHERE |
| MORE THAN ONE EXIT, EXIT ACCESS, OR EXIT DISCHARGE IS |
| REQUIRED, SUCH EXITS, EXIT ACCESSES, OR EXIT DISCHARGES |
| SHALL BE EXEMPT FROM THE DIAGONAL MEASUREMENT |
| SEPARATION DISTANCE CRITERIA OF 7.5.1.3.2 AND |
| 7.5.1.3.3, PROVIDED THAT SUCH EXITS, EXIT ACCESSES, OR |
| EXIT DISCHARGES ARE REMOTELY LOCATED IN ACCORDANCE WITH |
| 7.5.1.3.1. PER NFPA 101 SECTION 7.5.1.3.1 WHERE MORE |
| THAN ONE EXIT, EXIT ACCESS, OR EXIT DISCHARGE IS |
| REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH |
| EXITS, EXIT ACCESSES, OR EXIT DISCHARGES SHALL BE |
| REMOTELY LOCATED FROM EACH OTHER AND BE ARRANGED TO |
| MINIMIZE THE POSSIBILITY THAT MORE THAN ONE HAS THE |
| POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER |
| EMERGENCY CONDITION. |
| |
| SHEET FA1.1: PROVIDE A FIRE ALARM NOTIFICATION |
| APPLIANCE IN THE LARGE STORAGE ROOM (#103). |
| |
| FIRE SPRINKLER: FOR ISSUANCE OF A GENERAL BUILDING |
| PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING |
| CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION |
| DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE |
| AUTOMATIC FIRE SPRINKLERS. AFTER THE BUILDING PERMIT |
| HAS BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT |
| SHOP DRAWINGS (CONFORMING TO THE ENGINEERED |
| CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. |
| |
| WESLEY JOLIN |
| FIRE INVESTIGATOR & INSPECTOR |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 805-6730 |
| |