Plan Review Notes
Plan Review Notes For Permit 13120143
Permit Number 13120143
Review Stop B
Sequence Number 1
Notes
Date Text
2013-12-20 17:41:22BUILDING PLAN REVIEW
 PERMIT: 13120143
 ADD: 501 S FLAGLER DR # 301
 CONT: ANDERSON MOORE
 TEL: (561)662-1819
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY DEC. 20/ 2013
 ACTION: DENIED
  
 1) THE COVERSHEET (LIFESAFETY PLAN) NOR A-1.0 INDICATE
 COMPLIANCE WITH THE 2010 FLORIDA EXISTING BUILDING CODE
 703.2.2 SUPPLEMENTAL SHAFT AND FLOOR OPENING ENCLOSURE
 REQUIREMENTS. WHERE THE WORK AREA ON ANY FLOOR EXCEEDS
 50 PERCENT OF THAT FLOOR AREA, THE ENCLOSURE
 REQUIREMENTS OF SECTION 703.2 SHALL APPLY TO VERTICAL
 OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE FLOOR.
  
 PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 708.14.1
 ELEVATOR LOBBY.
 AN ENCLOSED ELEVATOR LOBBY SHALL BE PROVIDED AT EACH
 FLOOR WHERE AN ELEVATOR SHAFT ENCLOSURE CONNECTS MORE
 THAN THREE STORIES. THE LOBBY ENCLOSURE SHALL SEPARATE
 THE ELEVATOR SHAFT ENCLOSURE DOORS FROM EACH FLOOR BY
 FIRE PARTITIONS. IN ADDITION TO THE REQUIREMENTS IN
 SECTION 709 FOR FIRE PARTITIONS, DOORS PROTECTING
 OPENINGS IN THE ELEVATOR LOBBY ENCLOSURE WALLS SHALL
 ALSO COMPLY WITH SECTION 715.4.3 AS REQUIRED FOR
 CORRIDOR WALLS AND PENETRATIONS OF THE ELEVATOR LOBBY
 ENCLOSURE BY DUCTS AND AIR TRANSFER OPENINGS SHALL BE
 PROTECTED AS REQUIRED FOR CORRIDORS IN ACCORDANCE WITH
 SECTION 716.5.4.1. ELEVATOR LOBBIES SHALL HAVE AT LEAST
 ONE MEANS OF EGRESS COMPLYING WITH CHAPTER 10 AND OTHER
 PROVISIONS WITHIN THIS CODE. ALSO SEE THE 7 EXCEPTIONS.
  
 PLEASE REVIEW: MEMORANDUM CONCERNING ELEVATOR LOBBIES
 IN EXISTING HIGH RISE CONSTRUCTION
  
 TO: ALL INTERESTED PERSONS
  
 FROM: DOUG WISE, CONSTRUCTION SERVICES DIRECTOR,
 BUILDING OFFICIAL
  MIKE CARSILLO, BATTALION CHIEF FIRE RESCUE, FIRE
 MARSHAL
  
 RE: ELEVATOR LOBBIES IN EXISTING HIGH RISE
 CONSTRUCTION
  
 DATE: JANUARY 3, 2011
  
 IT HAS RECENTLY BEEN BROUGHT TO OUR ATTENTION THAT MANY
 EXISTING HIGH RISE STRUCTURES IN OUR COMMUNITY WERE
 INITIALLY CONSTRUCTED OR HAVE BEEN SUBSEQUENTLY
 MODIFIED SO AS TO BE WITHOUT ?ELEVATOR LOBBIES?.
 ELEVATOR LOBBIES ARE FIRE RATED ENCLOSURES, ENCLOSING
 THE ELEVATOR SHAFT ITSELF WITH EACH FLOOR ABOVE THE
 FIRST FLOOR. THE LACK OF AN ELEVATOR LOBBY CAN, UNDER
 CERTAIN CONDITIONS, CONSTITUTE A SERIOUS CONCERN BY
 CREATING INCREASED POTENTIAL FOR SPREAD OF SMOKE OR
 FIRE THOUGH AN EXISTING HIGH RISE STRUCTURE DURING A
 FIRE EVENT.
 RESEARCH BY CITY STAFF INDICATES THE REQUIREMENT FOR
 RATING OF ELEVATOR SHAFT ENCLOSURES WAS CLEARLY
 IDENTIFIED IN THE 1929 CITY OF WEST PALM BEACH BUILDING
 CODE IN SECTIONS 1807 AND 1907 RESPECTIVELY, FOR TYPE I
 AND TYPE II STRUCTURES OVER THREE (3) STORIES, AS TWO
 (2) HOURS MINIMUM, AND ONE (1) HOUR FOR TYPE III
 STRUCTURES (SEE ATTACHED EXHIBIT 1). BY 1965 THE
 SOUTHERN STANDARD BUILDING CODE IN EFFECT IN THE CITY
 REQUIRED ELEVATOR ENCLOSURES WHICH ENCLOSED NOT MORE
 THAN THREE (3) ELEVATORS TO BE ENCLOSED IN TWO (2) HOUR
 RATED ENCLOSURES IN A SINGLE SECTION WHICH WAS SECTION
 701.3 (SEE EXHIBIT 2). INTERESTINGLY, THE TERM
 ?ELEVATOR LOBBY? ITSELF DOES NOT APPEAR IN THE BUILDING
 CODE ITSELF UNTIL SOMETIME BETWEEN THE 1973 AND 1978
 EDITIONS. HOWEVER, AS PREVIOUSLY STATED, THE
 REQUIREMENT FOR FIRE RATING ELEVATOR SHAFT ENCLOSURES
 AND ALL OPENINGS THERETO DATES AS FAR BACK AS 1929. THE
 1965 CODE ALSO REQUIRED THAT, ?THE PATH OF TRAVEL FROM
 ONE FLIGHT OF STAIRS TO THE NEXT SHALL NOT PASS
 DIRECTLY IN FRONT OF ELEVATOR DOORS.? THIS CRITERIA IS
 CONSISTENT WITH CURRENT CODE REQUIREMENT WHICH PROVIDES
 THAT ONLY ONE OF THE TWO REQUIRED STAIRS MAY OPEN INTO
 THE ELEVATOR LOBBY AND THAT EACH TENANCY IN A MULTIPLE
 TENANT CONDITION SHALL HAVE ACCESS TO BOTH STAIRS, AT
 LEAST ONE OF WHICH MAY BE ACCESSED WITHOUT PASSING
 THROUGH THE ELEVATOR LOBBY.
 TO SUMMARIZE CITY STAFF?S RESEARCH, THE REQUIREMENT FOR
 FIRE RATING OF AN ELEVATOR SHAFT ENCLOSURE HAS BEEN
 IDENTIFIED TO EXIST IN EVERY BUILDING CODE ADOPTED IN
 THIS CITY FROM THE 1930?S TO THE PRESENT DAY WITH ONLY
 ONE NOTABLE EXCEPTION. ON OCTOBER 1, 2005 WITH THE
 ENACTMENT OF THE 2004 FLORIDA BUILDING CODE, THE
 REQUIREMENT WAS AMENDED TO ALLOW THE ELIMINATION OF THE
 FIRE RATED ENCLOSURE IF THE CORRIDOR INTO WHICH THE
 ELEVATOR OPENED WAS NOT REQUIRED ITSELF TO BE RATED
 (SEE EXHIBIT 3). THIS REQUIREMENT WAS AMENDED AGAIN ON
 DECEMBER 8, 2006 WITH THE FIRST ?BLUE PAGE? AMENDMENTS
 TO THE 2004 FLORIDA BUILDING CODE (SEE EXHIBIT 4) WHICH
 RE-INSTITUTED THE REQUIREMENT FOR A FIRE RATED ELEVATOR
 LOBBY WITH THE SPECIFIC LIMITED EXCEPTIONS THAT EXIST
 TODAY (SEE EXHIBIT 5). THIS MEANS THAT BUILDINGS WHICH
 DO NOT MEET THE CURRENT (OR 1929) CODE MAY BE DEEMED
 ?LEGALLY-EXISTING NON-CONFORMING? IF A PERMIT WHICH
 DEMONSTRATES THE ELIMINATION OF SUCH A LOBBY CAN BE
 EVIDENCED WHICH WAS ISSUED ONLY DURING THE
 ABOVE-REFERENCED NARROW ?WINDOW? OF TIME BETWEEN
 OCTOBER 1, 2005 AND DECEMBER 8, 2006. HOWEVER, EVEN
 LEGALLY-EXISTING NON-CONFORMITIES MUST ALSO BE
 ADDRESSED AS RENOVATIONS OCCUR IN ACCORDANCE THE TERMS
 THAT FOLLOW.
 TO BETTER PREPARE BUILDING OWNERS, MANGERS, OPERATORS,
 AND DESIGN PROFESSIONALS TO ANTICIPATE AND ADDRESS
 THESE SPECIFIC CODE REQUIREMENTS, THE CONSTRUCTION
 SERVICES DEPARTMENT AND FIRE PREVENTION DEPARTMENT
 PROPOSE TO ADDRESS THE ABSENCE OF AN ELEVATOR LOBBY
 (WHEN REQUIRED) AS FOLLOWS:
  
 1.1. IF A TENANT IMPROVEMENT IS SUBMITTED WHICH
 PROPOSES TO RECONFIGURE THE ENTIRE EXISTING BUILDING
 FLOOR, AN ELEVATOR LOBBY, OR COMPLIANCE WITH ONE OF THE
 SIX (6) EXCEPTIONS ALLOWED UNDER THE PRESENT CODE WILL
 BE REQUIRED. THIS IS REGARDLESS OF WHETHER OR NOT THE
 ABSENCE OF AN ELEVATOR LOBBY CAN BE DEMONSTRATED WITH A
 VALID PERMIT ISSUED BETWEEN OCTOBER 1, 2005 AND
 DECEMBER 8, 2006.
 1 2. IF A TENANT IMPROVEMENT IS SUBMITTED WHICH
 PROPOSES TO RECONFIGURE A PORTION OF THE EXISTING
 BUILDING FLOOR AREA, WITH NO WORK BEING PROPOSED IN THE
 AREA OF THE ELEVATOR LOBBY, AND NO ELEVATOR LOBBY IS
 FOUND TO EXIST ON THE FLOOR, AND A VALID PERMIT CAN BE
 EVIDENCED WHICH WAS ISSUED BETWEEN OCTOBER 1, 2005 AND
 DECEMBER 8, 2006, THE TENANT IMPROVEMENT PERMIT MAY BE
 APPROVED AND THE BUILDING SHALL REMAIN AS LAWFULLY
 CONFIGURED UNTIL THE MAJORITY OF THE EXISTING FLOOR
 PLAN, OR THE ELEVATOR LOBBY AREA ITSELF UNDERGOES
 RENOVATION.
 1.3. IF A TENANT IMPROVEMENT IS SUBMITTED WHICH
 PROPOSES TO RECONFIGURE A PORTION OF THE EXISTING
 BUILDING FLOOR AREA, WITH NO WORK BEING PROPOSED IN THE
 AREA OF THE ELEVATOR LOBBY, AND NO ELEVATOR LOBBY IS
 FOUND TO EXIST ON THE FLOOR, AND NO VALID PERMIT CAN BE
 EVIDENCED WHICH WAS ISSUED BETWEEN OCTOBER 1, 2005 AND
 DECEMBER 8, 2006, THE TENANT IMPROVEMENT PERMIT MAY BE
 APPROVED. THE BUILDING OWNER WILL BE NOTIFIED OF AN
 UNSAFE CONDITION ON THE EXISTING STRUCTURE BY THE CITY
 FIRE MARSHAL?S OFFICE AND ASKED TO UNDERTAKE
 APPROPRIATE ACTIONS TO CORRECT THE SITUATION.
 1.4. IF ANY RECONFIGURATION IS PROPOSED WHICH AFFECTS
 THE ELEVATOR LOBBY AREA ITSELF, AN ELEVATOR LOBBY, OR
 COMPLIANCE WITH ONE OF THE SIX (6) EXCEPTIONS LISTED IN
 THE CODE SHALL BE REQUIRED.
  
 IT SHOULD BE NOTED THAT CITY STAFF REMAINS COMMITTED TO
 ASSISTING BUILDING OWNERS, MANAGERS, AND DESIGN
 PROFESSIONALS IN SUCCEEDING IN CREATING AND MAINTAINING
 SAFE PLACES TO LIVE AND WORK IN OUR COMMUNITY. WE ARE
 READY AND WILLING TO PROVIDE TECHNICAL ASSISTANCE IN
 UNDERSTANDING THE OFTEN COMPLEX CRITERIA THAT AFFECT
 EXISTING AND NEW HIGH RISE BUILDINGS. IT MUST BE STATED
 THAT THE SIMPLE INSTALLATION OF A HOIST-WAY
 PRESSURIZATION SYSTEM MAY BE ONE POTENTIAL METHOD TO
 ELIMINATE THE NEED FOR AN ELEVATOR LOBBY THROUGHOUT AN
 ENTIRE BUILDING. ANOTHER ALTERNATIVE IS TO INSTALL FIRE
 SHUTTERS AT THE ELEVATOR DOOR OPENINGS. THESE
 METHODOLOGIES MAY OFFER THE ADDED POTENTIAL TO INCREASE
 THE LEASABLE FLOOR AREA WITHIN THESE BUILDINGS.
  
 PLEASE FEEL FREE TO CONTACT US DIRECTLY IF WE CAN
 ASSIST YOU FURTHER IN UNDERSTANDING THESE CRITERIA AND
 HELP YOU TO ENSURE THE SAFETY OF YOUR RESIDENTS,
 TENANTS, AND PROPERTY.
 DOUG WISE ? 805-6650 ? [email protected]
 MIKE CARSILLO ? 804-4709 ? [email protected]
  
  
 : WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved