2013-12-26 17:33:43 | BECAUSE THIS EQUIPMENT WILL BE IN PLACE FOR AN EXTENDED | | PERIOD YOU SHALL: | | 1. PROVIDE A SITE DRAWING INDICATING THE LOCATION OF | | BOTH THE TRANSFORMER AND THE EQUIPMENT REFLECTED ON THE | | DRAWING. | | 2. THIS APPARATUS IS NOT FREE STANDING, AND THEREFORE | | YOU MUST SHOW HOW WILL THIS BE SUPPORTED. IF THIS IS TO | | BE MOUNTED ON A POLE OR A SITE BUILT RACK, YOU MUST | | PROVIDE ENGINEERED DRAWINGS SHOWING COMPLIANCE WITH | | WIND LOADS. | | 3. ALL RECEPTACLES SHALL BE GFCI PROTECTED AND COMPLY | | WITH NEC 406.8. |
|