2014-01-02 16:32:30 | THE APPLICATION DOES NOT PROVIDE AMPLE DETAIL AS TO THE | | WORK BEING PERFORMED | | YOU WILL NEED TO PROVIDE THE FOLLOWING FOR THE ISSUANCE | | OF AN ELECTRICAL PERMIT: | | 1. LOCATION OF POWER SOURCE FOR THE BOAT LIFT. | | 2. HOW WILL POWER BE TAKEN TO THE LIFT MOTORS. | | 3. SIZE AND QUANTITY OF LIFT MOTORS. | | 4. AS PER NEC 210.8 GFI PROTECTION SHALL BE PROVIDED | | FOR BOAT HOISTS | | 5. ALL TRENCHING SHALL COMPLY WITH NEC 300.5 AND BE | | INSPECTED PRIOR TO ANY BACK FILL. | | 6. THERE MUST BE A 120 VOLT 20 AMP GFCI OUTLET WITHIN | | CLOSE PROXIMITY OF THE LIFT. | | | | ALL ELECTRICAL WORK ON THIS PERMIT | | SHALL COMPLY WITH ALL THE REQUIREMENTS | | OF THE 2008 EDITION OF THE NEC. | | |
|