Plan Review Notes For Permit 13120070 |
Permit Number |
13120070 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-12-19 12:31:08 | ONLY ONE SET OF THE PLANS WAS STAMPED DUE TO THE | | POSSIBILITY OF HAVING TO RESUBMIT DUE TO ENGINEER SEAL: | | THESE PLANS WERE CONDITIONALLY APPROVED, AND THE | | FOLLOWING CORRECTIONS HAVE TO BE MADE TO THE NEWLY | | SUBMITTED PLANS OR CORRECTED IN THE FIELD FOR | | COMPLIANCE: | | PG. E0.2 FAILS TO INDICATE THE PROPER SPACING FOR THE | | ELECTRICAL APPARATUS, THUS CONFORMANCE WITH NEC 110 | | REQUIREMENTS SHALL BE ADHERED TO. | | PG. E2.1 MENTIONS AN ENLARGED VIEW OF THE ROOM WHICH IS | | MISSING, THEREFORE PRECISE DETAIL IS DIFFICULT TO | | DETERMINE FROM THE PLANS, PROPER SPACING AND LOCATION | | OF THE MANDATORY ITEMS WILL BE REQUIRED. | | PG. E4.1 FEEDER #28 IS COMPOSED OF 2 PARALLEL 250 KCMIL | | CONDUCTORS TOTALING 500 KCMILS THUS AS PER NEC TABLE | | 250.66 A 1/0 EGC IS REQUIRED. | | PG. E4.1 THERE APPEARS TO BE A TYPO BELOW ICATHB | | DESIGNATION SOURCE OF POWER AS "ATS1" YET THE DRAWING | | REFLECTS "ATS11" | | | | THE ABOVE MENTIONED SHALL BE ADDRESSED AS HEREIN | | DESCRIBED. |
|