Plan Review Notes
Plan Review Notes For Permit 13120070
Permit Number 13120070
Review Stop E
Sequence Number 1
Notes
Date Text
2013-12-19 12:31:08ONLY ONE SET OF THE PLANS WAS STAMPED DUE TO THE
 POSSIBILITY OF HAVING TO RESUBMIT DUE TO ENGINEER SEAL:
 THESE PLANS WERE CONDITIONALLY APPROVED, AND THE
 FOLLOWING CORRECTIONS HAVE TO BE MADE TO THE NEWLY
 SUBMITTED PLANS OR CORRECTED IN THE FIELD FOR
 COMPLIANCE:
 PG. E0.2 FAILS TO INDICATE THE PROPER SPACING FOR THE
 ELECTRICAL APPARATUS, THUS CONFORMANCE WITH NEC 110
 REQUIREMENTS SHALL BE ADHERED TO.
 PG. E2.1 MENTIONS AN ENLARGED VIEW OF THE ROOM WHICH IS
 MISSING, THEREFORE PRECISE DETAIL IS DIFFICULT TO
 DETERMINE FROM THE PLANS, PROPER SPACING AND LOCATION
 OF THE MANDATORY ITEMS WILL BE REQUIRED.
 PG. E4.1 FEEDER #28 IS COMPOSED OF 2 PARALLEL 250 KCMIL
 CONDUCTORS TOTALING 500 KCMILS THUS AS PER NEC TABLE
 250.66 A 1/0 EGC IS REQUIRED.
 PG. E4.1 THERE APPEARS TO BE A TYPO BELOW ICATHB
 DESIGNATION SOURCE OF POWER AS "ATS1" YET THE DRAWING
 REFLECTS "ATS11"
  
 THE ABOVE MENTIONED SHALL BE ADDRESSED AS HEREIN
 DESCRIBED.