2014-01-13 09:18:242010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF HVAC EQUIPMENT SIZING
 CALCULATIONS AS REQUIRED BY FBCR M1401.3
  
 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS. FBC ENERGY
 CONSERVATION SECTION 101.4.1
  
 3) SPECIFY THE GRILL SIZE AND CFMS AT EACH OF THE
 SUPPLY OUTLETS. FBCR M1601.1 AND CITY AMENDMENTS
 107.3.5.3
  
 4) SPECIFY THE SIZE OF EACH OF THE GRILLS FOR THE
 RETURN AIR TRANSFER DUCTS ON THE PLANS. FBCR M1602
  
 5) SPECIFY THE SIZE AND LOCATION OF THE RETURN AT THE
 AIR HANDLER CLOSET. IF THE RETURN IS THROUGH A LOUVER
 DOOR SPECIFY THIS ON THE PLANS. FBCR M1602
  
 6) THE TRANSFER DUCT SIZES SPECIFIED ON THE PLANS ARE
 TOO SMALL. FBCR M1602.4 REQUIRES THE TRANSFER DUCTS TO
 BE 1-1/2 TIMES THE CROSS SECTIONAL AREA OF THE SUPPLY
 DUCT ENTERING THE ROOM.
  
 7) PROVIDE AN HVAC EQUIPMENT SCHEDULE ON THE MECHANICAL
 PLANS. SPECIFY THE A/H AND CONDENSER MODEL NUMBERS,
 ELECTRICAL REQUIREMENTS, BREAKER SIZES, TOTAL CFMS,
 HEATING AND COOLING BTUS, ETC.
  
 8) REVISE PLANS TO SHOW A SERVICE RECEPTACLE OUTLET AT
 OR NEAR EACH OF THE CONDENSING UNITS. FBCR M1305.1.4.3
  
 9) ON THE PLANS, PROVIDE AN ANCHORING DETAIL FOR THE
 CONDENSING UNITS THAT IS CAPABLE OF RESISTING A 170 MPH
 WIND SPEED. FBCR M1307.2.1
  