Plan Review Notes For Permit 13120015 |
Permit Number |
13120015 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-01-13 09:18:24 | 2010 FBC | | | | DENIED BY MECHANICAL | | | | 1) SUBMIT TWO SETS OF HVAC EQUIPMENT SIZING | | CALCULATIONS AS REQUIRED BY FBCR M1401.3 | | | | 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS. FBC ENERGY | | CONSERVATION SECTION 101.4.1 | | | | 3) SPECIFY THE GRILL SIZE AND CFMS AT EACH OF THE | | SUPPLY OUTLETS. FBCR M1601.1 AND CITY AMENDMENTS | | 107.3.5.3 | | | | 4) SPECIFY THE SIZE OF EACH OF THE GRILLS FOR THE | | RETURN AIR TRANSFER DUCTS ON THE PLANS. FBCR M1602 | | | | 5) SPECIFY THE SIZE AND LOCATION OF THE RETURN AT THE | | AIR HANDLER CLOSET. IF THE RETURN IS THROUGH A LOUVER | | DOOR SPECIFY THIS ON THE PLANS. FBCR M1602 | | | | 6) THE TRANSFER DUCT SIZES SPECIFIED ON THE PLANS ARE | | TOO SMALL. FBCR M1602.4 REQUIRES THE TRANSFER DUCTS TO | | BE 1-1/2 TIMES THE CROSS SECTIONAL AREA OF THE SUPPLY | | DUCT ENTERING THE ROOM. | | | | 7) PROVIDE AN HVAC EQUIPMENT SCHEDULE ON THE MECHANICAL | | PLANS. SPECIFY THE A/H AND CONDENSER MODEL NUMBERS, | | ELECTRICAL REQUIREMENTS, BREAKER SIZES, TOTAL CFMS, | | HEATING AND COOLING BTUS, ETC. | | | | 8) REVISE PLANS TO SHOW A SERVICE RECEPTACLE OUTLET AT | | OR NEAR EACH OF THE CONDENSING UNITS. FBCR M1305.1.4.3 | | | | 9) ON THE PLANS, PROVIDE AN ANCHORING DETAIL FOR THE | | CONDENSING UNITS THAT IS CAPABLE OF RESISTING A 170 MPH | | WIND SPEED. FBCR M1307.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|