2014-01-13 09:23:332010 FBC / 2008 NEC
  
 DENIED BY ELECTRICAL
  
 1) THE ELECTRICAL PANEL LOCATED NEXT TO THE KITCHEN
 SINK IS REQUIRED TO BE RE-LOCATED (IT CAN BE REVERSED
 TO FACE TOWARD THE LIVING ROOM). NEC 240.24(A)
  
 2) AN ELECTRICAL RECEPTACLE OUTLET IS REQUIRED WITHIN
 25 FEET OF EACH A/C CONDENSERS FOR SERVICE. NEC 210.63
  
 3) THE BATHROOM AND KITCHEN RECEPTACLES SERVICING THE
 COUNTERTOPS ARE REQUIRED TO BE GFCI PER NEC 210.8.
  
 4) RECEPTACLE OUTLET SPACING IN THE UNITS IS REQUIRED
 TO COMPLY WITH NEC 210.52.
  
 5) TAMPER RESISTANT RECEPTACLES ARE REQUIRED PER NEC
 406.11.
  
 6) AFCI PROTECTION IS REQUIRED PER 210.12.
  
 7) THE REQUIRED SMOKE ALARM IS NOT SHOWN FOR THE NEWLY
 CREATED BEDROOM. FBC R314.
  
 NOTE: PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW
 EACH OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  