2013-12-09 11:26:43 | 2010 FBC |
| |
| |
| REVISION TO PERMIT #12060082 |
| DENIED BY BUILDING |
| |
| 1) PLAN SHEET A-3 SPECIFIES A NEW ASPHALT SHINGLE ROOF |
| OVER HOT MOPPED 15# FELT ON A LOW SLOPE ROOF THAT |
| APPEARS TO BE LESS THAN A 2 : 12 SLOPE. SPECIFY THE |
| ROOF SLOPE ON THE PLANS AND PROVIDE PRODUCT APPROVALS |
| FOR THE ROOF ASSEMBLY AS REQUIRED BY DCA RULE 9N-3. THE |
| MINIMUM SLOPE FOR ASPHALT SHINGLES IS 2 : 12 PER FBC |
| R905.2.2. |
| |
| 2) THE TWO (2) NEW SH24 SINGLE HUNG WINDOWS THAT ARE |
| SPECIFIED FOR THE PROPOSED SECOND FLOOR BEDROOM THAT |
| WILL BE CONVERTED FROM THE EXISTING PORCH DO NOT COMPLY |
| WITH FBC R310 FOR THE REQUIRED EMERGENCY ESCAPE AND |
| RESCUE OPENING. |
| |
| 3) SUBMIT TWO (2) COPIES OF PRODUCT APPROVALS FOR THE |
| SINGLE HUNG WINDOWS, THE STRUCTURAL MULLION BETWEEN |
| THEM AND THE STRUCTURAL FRAMING CONNECTORS AS REQUIRED |
| BY DCA RULE 9N-3. |
| |
| 4) ALL PRODUCT APPROVALS SUBMITTED TO THE CITY OF WEST |
| PALM BEACH ARE REQUIRED TO BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD. CITY AMENDMENTS |
| 107.3.4.1 |
| |
| 5) THE WALL SECTION ON SHEET A-3 OF THE PLANS SHOWS A 2 |
| X 6 WOOD FRAME SINGLE ASSEMBLY ROOF/CEILING WITH R-30 |
| BATT INSULATION. THE MINIMUM THICKNESS FOR R-30 BATT |
| INSULATION IS 8-1/4" AND FBC R806.3 REQUIRES A MINIMUM |
| 1-INCH AIR SPACE BETWEEN THE ROOF SHEATHING AND THE |
| INSULATION. FBC R806.1 REQUIRES EACH ENCLOSED RAFTER |
| SPACE TO BE VENTED. SHOW COMPLIANCE WITH FBC R 806 OR |
| PROVIDE A DESIGN IN COMPLIANCE WITH FBC R806.4 FOR AN |
| UNVENTED ATTIC ASSEMBLY. |
| |
| 6) FBC R 703.6.3 REQUIRES A BOND BREAK BETWEEN THE |
| EXTERIOR WALL STUCCO AND THE WATER-RESISTIVE BARRIER |
| REQUIRED BY FBC R703.2. |
| |
| 7) ON SHEET PE-1 THE GARAGE FLOOR PLAN HAS A NOTE AT |
| THE METER LOCATION STATING THAT THERE IS AN EXISTING |
| 125 AMP MAIN HOUSE DISCONNECT IN EXISTING 1/2" CONDUIT |
| TO THE MAIN HOUSE PANEL. THE MAIN HOUSE HAS A 200 AMP |
| PANEL. PLEASE CLARIFY. NEC 230 IV AND VI |
| |
| 8) ONE OF THE REVISED PLANS WILL BE REQUIRED TO BE |
| SIGNED OUT AND TAKEN TO PALM BEACH COUNTY FOR AN IMPACT |
| FEE REVIEW. THE PLAN WITH THE IMPACT REVIEW STAMP AND A |
| COPY OF THE PAID IMPACT FEE RECEIPT IS TO BE RETURNED |
| TO THE CITY BUILDING DEPARTMENT. |
| |
| 9) A SMOKE ALARM IS REQUIRED OUTSIDE THE SLEEPING AREA |
| IN THE IMMEDIATE AREA OF THE BEDROOMS PER FBC R314.3 |
| AND A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN |
| FEET OF EACH SLEEPING ROOM PER FBC R315. |
| |
| PLEASE SUBMIT A RESPONSE LETTER WHEN RESUBMITTING THIS |
| REVISON, INDICATING HOW EACH OF THE REVIEW COMMENTS WAS |
| ADDRESSED. |
| |