2013-12-27 14:05:16 | BUILDING PLAN REVIEW |
| PERMIT: 13110818 |
| ADD: 1016 CLARE AVE. SUITES 1 & 2 |
| CONT: POLO CONSTRUCTION |
| TEL: (561)239-8607 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRIDAY DEC. 27/ 2013 |
| ACTION: DENIED |
| |
| 1) SHEET A1.0 MISSING INFORMATION: |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.3.5 |
| MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| |
| 1A) OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| SHALL BE DETERMINED. PLEASE PROVIDE A NARRATIVE AS TO |
| USAGE IT APPEARS THERE IS A MERCANTILE & BUSINESS |
| OCCUPANCY WITH STORAGE AS A ACCESSORY OCCUPANCY AS WELL |
| AS A SEPERATE STORAGE OCCUPANCY. PLEASE PROVIDE AS TO |
| IF THE STORAGE OCCUPANCY IS A S1 OR S2 OCCUPANCY. |
| |
| 1B) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| (SEE TABLE 503). THIS PROPERTY IS HAD UP OF 4 BUILDINGS |
| WITH 4 HOUR FIRE WALLS. PLEASE PROVIDE THE MINIMUM |
| BUILDING TYPE IF BUILDING AREA MODIFICATIONS, FRONTAGE |
| (FBC-B 506.2) AND OR SPRINKLER INCREASES (FBC-B 506.3) |
| WERE TAKEN IN DETERMINING MINIMUM BUILDING TYPE. SEE |
| FBC-B 506.1 FOR BUILDING INCREASE FORMULA. |
| FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE |
| THE FOLLOWING COMPONENTS: |
| FIRE-RESISTANT SEPARATIONS |
| FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| |
| 1C) UNTIL TYPE OF CONSTRUCTION IS DETERMINED, THE WALL |
| BETWEEN THE MERCANTILE PORTION AND SEPERATE STORAGE |
| OCCUPANCY CAN NOT BE DETERMINED IF THIS IS A OCCUPANCY |
| SEPERATION WALL OR IF IT IS A FIRE WALL CREATING |
| SEPERATE BUILDINGS PER FBC-B 706.4 & TABLE 706.4 AND |
| OPENING PROTECTIVES PER 715.4. |
| |
| 1D) THE LIFE SAFETY SHEET DOES NOT DECLARE THIS TO BE A |
| FIRE SPRINKLERED BUILDING ALTHOUGH THE INDEX INDICATES |
| FIRE SPRINKLER PLANS ARE INCLUDED. |
| |
| 1E) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| OCCUPANCY LOAD |
| GROSS |
| NET |
| MEANS OF EGRESS |
| EXIT ACCESS |
| EXIT |
| EXIT DISCHARGE |
| DOORS |
| EMERGENCY LIGHTING AND EXIT SIGNS |
| SPECIFIC OCCUPANCY REQUIREMENTS |
| CONSTRUCTION REQUIREMENTS |
| |
| NOTE SHEET D1.0 INDICATES 1/4 INCH SCALE WHEREAS A1.0 |
| INDICATES 1/8 TH SCALE, PLANS INDICATE 13,330 SQ FT IN |
| THE S1 OCCUPANCY SCALING IT OFF THE PALNS BOTH SECTIONS |
| OF THE BUILDING ARE APPROXIMATELY 9409 SQ FT OR AROUND |
| 18, 818 SQ FT. |
| |
| 2) SHEET 01: |
| 2A) NEW ENTRY NORTH WALL GRADING DETAIL INDICATES THE |
| EXISTING GRADE TO BE 17.69 AND THE FINISH FLOOR GRADE |
| IS 18.10. PLEASE PROVIDE DETAILS HOW THE DIFFERENCE IN |
| GRADE WILL BE MADE UP, THE DETAILS WILL DETERMINE IF |
| THIS AREA WILL BE CONSIDERED A RAMP OR JUST GRADE. IF |
| THE RUNNING SLOPE OF THE WALKING SURFACE IS NOT STEEPER |
| THAN 1:20 THEN IT WILL NOT BE CONSIDERED A RAMP SEE |
| 2010 FBC-B 403.2. |
| |
| 2B) THE NORTH ENTRY NEITHER THE CROSSWALK OR EXIT FROM |
| THE BUILDING INDICATES THAT YOU ARE CROSSING A |
| VEHICULAR LANE. SEE DETECTABLE WARNING. FL |
| ACCESSIBILITY 106.5 A STANDARDIZED SURFACE FEATURE |
| BUILT IN OR APPLIED TO WALKING SURFACES OR OTHER |
| ELEMENTS TO WARN OF HAZARDS ON A CIRCULATION PATH. |
| |
| 3) SHEET S-2 PLEASE REVIEW THE DESIGN CRITERIA FOR THIS |
| PROJECT TYPE VB AND GROUP R-3 OCCUPANCY. |
| |
| 4) PLEASE PROVIDE THE WIND DESIGN CRITEIA: 2010 FBC-B |
| 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF |
| ASCE 7-10. |
| 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| 1609.3 WIND SPEED CONVERSION |
| 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| |
| 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| |
| 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| |
| 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| |
| 3.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| TABLE 1609.2(2) . |
| |
| 5) THE PLANS INDICATE A MERCANTILE PORTION OF THE |
| TENANT SPACE PLEASE PROVIDE COMPLIANCE WITH THE 2010 |
| FBC ACCESSIBILITY CODE: |
| 904.3 CHECK-OUT AISLES. |
| CHECK-OUT AISLES SHALL COMPLY WITH 904.3. |
| 904.3.1 AISLE. |
| AISLES SHALL COMPLY WITH 403. |
| 904.3.2 COUNTER. |
| THE COUNTER SURFACE HEIGHT SHALL BE 38 INCHES (965 MM) |
| MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. THE TOP OF |
| THE COUNTER EDGE PROTECTION SHALL BE 2 INCHES (51 MM) |
| MAXIMUM ABOVE THE TOP OF THE COUNTER SURFACE ON THE |
| AISLE SIDE OF THE CHECK-OUT COUNTER. |
| FIGURE 904.3.2 |
| CHECK-OUT AISLE COUNTERS |
| 904.3.3 CHECK WRITING SURFACES. |
| WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY |
| WITH 902.3. |
| 904.4 SALES AND SERVICE COUNTERS. |
| SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH |
| 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE |
| COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR |
| SERVICE COUNTER TOP. |
| |
| 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |