2013-12-10 18:51:22THE FOLLOWING CORRECTIONS NEED TO BE MADE FOR THE NEXT
 PLAN REVIEW:
 1.PROVIDE COMPLETE LITERATURE PACKAGE FOR GENERATOR AND
 TRANSFER GEAR.
 2. SHOW ELEVATIONS FOR THE METER ROOM IF INTENTIONS ARE
 TOP PLACE PANEL 6G BELOW EXISTING PANEL L2C
 3. INCLUDE A COMPLETE LEGEND FOR BETTER UNDERSTANDING
 OF YOUR RISER DIAGRAM
 4. PROVIDE LOAD CALC & A PANEL SCHEDULE FOR PANEL H6
 5. CORRECT THE NOMENCLATURE FOR THE TRANSFORMER, OR
 EXPLAIN WHAT A SINGLE PHASE TRANSFORMER IS DOING THERE.
 6. COMPLETE THE RISER DIAGRAM FOR THE PENTHOUSE LEVEL.