2013-12-03 11:04:306751 NORTH JOG ROAD - VISITOR'S CENTER
 TRACKING #13110774
 PERMIT #12080615
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE HYDRAULIC CALCULATIONS SUBMITTED ARE FOR THE 3RD
 FLOOR AREA (207 GPM @60 PSI); HOWEVER, THE 2ND FLOOR
 AREA INDICATES A GREATER HYDRAULICA DEMAND (360 GPM @72
 PSI). SUBMIT THE HYDRAULIC CALCULATIONS FOR THE SECOND
 FLOOR REMOTE AREA.
  
 SUBMIT AN ADDITIONAL SET OF HYDRAULIC CALCULATIONS
 UTILIZING ONLY CITY FLOW/PRESSURE AS THE VISITOR'S
 CENTER BUILDING HAS BEEN REQUESTED TO RECEIVE TEMPORARY
 OCCUPANCY BEFORE THE NEW FIRE PUMPS ARE TO BE
 INSTALLED, INPSECTED, TESTED, AND APPROVED.
  