Plan Review Notes
Plan Review Notes For Permit 13110725
Permit Number 13110725
Review Stop B
Sequence Number 2
Notes
Date Text
2014-03-21 13:35:57 
 ***REVIEW IN PROGRESS...
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) HARDIEPLANK SIDING AS SHOWN ON PLANS.
 ***NOA 07-0418.04 SUBMITTED EXPIRED ON MAY 01, 2012.
 NEED CURRENT NOA.
  
 B) HORIZONTAL SLIDER WINDOWS AS SHOWN IN THE NEW
 KITCHEN AREA.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. ***NOTE: PROVIDE ONLY THE PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR.
  
  
 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 3- SHEET 2 OF 3:
 A) THE COMPONENTS AND CLADDING DESIGN PRESSURES SHOWN
 FOR THE ROOF ARE INCORRECT. REVISE AS REQUIRED. SEE
 TABLE R301.2(2) OF 2010 FBC-RESIDENTIAL. ***NOTE: KEEP
 IN MIND THAT THIS TABLE IS FOR EXPOSURE "B". NEED TO
 ADJUST TO EXPOSURE "C" ACCORDINGLY.
 *** REVISED VALUES ARE INCORRECT. WORST CASE SCENARIO
 IS FOR ROOF ZONE #3. PROVIDE CALCULATIONS. SEC.
 107.2.1.3 CITY AMENDMENTS TO FBC.
  
 4- SECTION B-B ON SHEET 3 OF 3:
 A) NEED GUTTERS AS REQUIRED BY SEC. R318.6.
 ***PROVIDE COMPLETE INFORMATION. EXTERIOR REAR
 ELEVATION DOESN'T SHOW THE DOWNSPOUTS.
  
 5- NEW COMMENT: INSULATION CHANGED FROM BATT INSULATION
 TO ICYNENE INSULATION. PROVIDE ICYNENE ICC EVALUATION
 REPORT AND MANUFACTURER SPECS.
  
 6- ARCHITECT TO REVISE THE ENERGY CALCULATIONS (FORM
 402-2010 SUBMITTED THIS TIME) AND COORDINATE WITH FLOOR
 PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION:
 ***NOTES:
 A) CAREFULLY READ ALL THE GENERAL INSTRUCTIONS ON PAGE
 ONE AND ALL THE NOTES ON PAGE TWO. THEY SHOW ALL THE
 CONDITIONS THAT NEED TO BE MET IN ORDER TO USE THIS
 FORM. AND REVISE ACCORDINGLY.
  
 B) TOTAL ADDITION APPLIES TO THE NEW KITCHEN AREA AND
 THE AREA ENCLOSED BY THE PARTIALLY COVERED PORCH. TAKE
 THIS INTO CONSIDERATION FOR THE TOTAL ADDITION
 CONDITIONED AREA. THE NEW KITCHEN IS LOCATED IN AN
 EXISTING ENCLOSED PORCH. THIS AREA WAS NOT INSULATED.
 NEED TO INSULATE THE RAISED FLOOR, WALLS AND CEILING IN
 THIS AREA.
  
  
  
 ***NOTE:
 PLEASE PROVIDE A RESPONSE LETTER SHOWING HOW AND WHERE
 EACH COMMENT WAS ADDRESSED TO EXPEDITE THE REVIEW
 PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712