2014-01-06 09:53:10 | RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- THERE ARE TWO DIFFERENT SET OF PLANS SUBMITTED. ONE |
| WAS SIGNED AND SEALED BY THE ARCHITECT AND THE OTHER |
| ONE WAS NOT. ALL PLANS NEED TO BE SIGNED AND SEALED BY |
| THE ARCHITECT SHOWN ON THE TITLE BLOCK AS REQUIRED BY |
| CHAPTER 481 FL. ST.. CLARIFY WHICH SET OF PLANS IS THE |
| CORRECT ONE. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| |
| ***NOTE: ONLY THE SIGNED AND SEALED SET WAS REVIEWED. |
| COMMENTS APPLY TO THOSE DRAWINGS ONLY. |
| |
| 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT |
| FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY |
| OF PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY |
| IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| CODE. |
| |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) ROOF SHINGLES AS SHOWN ON PLANS. |
| |
| B) HARDIEPLANK SIDING AS SHOWN ON PLANS. INFORMATION |
| SUBMITTED IS THE MANUFACTURES SPECIFICATIONS, NOT AN |
| OFFICIAL PRODUCT APPROVAL. NEED EITHER MIAMI-DADE NOA |
| OR FLORIDA PRODUCT APPROVAL WITH THE CORRESPONDING |
| FLORIDA PRODUCT APPROVAL NUMBER. |
| |
| C) HORIZONTAL SLIDER WINDOWS AS SHOWN IN THE NEW |
| KITCHEN AREA. |
| |
| D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| AND DETAILS. ***NOTE: PROVIDE ONLY THE PRODUCT APPROVAL |
| COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR. |
| |
| 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| |
| 5- SHEET 2 OF 3: |
| A) THE COMPONENTS AND CLADDING DESIGN PRESSURES SHOWN |
| FOR THE ROOF ARE INCORRECT. REVISE AS REQUIRED. SEE |
| TABLE R301.2(2) OF 2010 FBC-RESIDENTIAL. ***NOTE: KEEP |
| IN MIND THAT THIS TABLE IS FOR EXPOSURE "B". NEED TO |
| ADJUST TO EXPOSURE "C" ACCORDINGLY. |
| |
| B) REVISE ALL THE LANDINGS TO COMPLY WITH SEC. R311.3 |
| OF 2010 FBC-RESIDENTIAL. |
| |
| 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS TO FBC. REVISE THE VALUATION. |
| |
| 7- SECTION B-B ON SHEET 3 OF 3: |
| A) SPECIFY ROOF PITCH AND SPECIFY TWO LAYERS OF |
| UNDERLAYMENT AS REQUIRED BY SEC. R905.2.2. |
| |
| B) R-19 BUTT INSULATION DOESN'T FIT ON 2X4 WALL. REVISE |
| AS REQUIRED. AND COORDINATE WITH THE ENERGY |
| CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| CONSERVATION. |
| |
| C) COORDINATE CEILING INSULATION WITH INFORMATION ON |
| THE ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010 |
| FBC-ENERGY CONSERVATION. |
| |
| C) NO GYPSUM BOARD ON CEILING?. PROVIDE FRAMING DETAILS |
| FOR NEW CEILING. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| |
| D) NEED GUTTERS AS REQUIRED BY SEC. R318.6. |
| |
| E) SPECIFY WEATHER RESISTANT SHEATHING PAPER AS |
| REQUIRED BY SEC. R703.2. |
| |
| 8- REVISE ROOF SHEATHING NOTE ON SHEET 3 OF 3. NEED |
| 4"0." NAILS ON GABLE END AS REQUIRED BY SEC. R803.2.3.1 |
| AND TABLE R803.2.3.1. |
| ***NOTE: ROOF ZONE #3 IS AT LEAST 5'-0" OF ENTIRE GABLE |
| END. SEE FIGURE R803.2.3.1. |
| |
| 9- SPECIFY ATTIC VENTILATION AS REQUIRED BY SEC. R806. |
| AND, COORDINATE WITH THE ENERGY CALCULATIONS. |
| |
| 10- REVISE ENERGY CALCULATIONS SUBMITTED AND COORDINATE |
| WITH FLOOR PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| CONSERVATION: |
| A) AREA WEIGHTED AVERAGE OVERHANG DEPTH SHOWN ON ITEM 7 |
| DOESN'T MATCH PLANS. |
| |
| B) REVISE FLOOR TYPE AND INSULATION TO MATCH REVISED |
| PLANS. (NEED INSULATION). TIS IS NOT A CONCRETE SLAB ON |
| GRADE. |
| |
| C) COORDINATE ROOF/ATTIC VENTILATION WITH REVISED |
| PLANS. |
| |
| D) REVISE ROOF MATERIAL ON PAGE 2 OF 5 TO MATCH PLANS. |
| |
| E) CLEARLY SPECIFY ACTUAL WINDOW ORIENTATION ON PAGE 3 |
| OF 5 TO MATCH PLANS. |
| |
| F) COMPLETE ALL THE INFORMATION ON TOP OF FORM. |
| |
| 11- ARCHITECT TO COORDINATE ALL PLANS WITH THE REVISED |
| ENERGY CALCULATIONS. COORDINATE INSULATION VALUE SHOWN |
| ON WALLS, CEILINGS, RAISED FLOOR. ALSO, COORDINATE THE |
| ROOF VENTILATION. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| CONSERVATION. |
| |
| ***NOTE: |
| PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561)805-6712 |