Plan Review Notes For Permit 13110678 |
Permit Number |
13110678 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-01-04 14:13:16 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 | | [email protected] | | | | FBC FLORIDA BUILDING CODE 2010 | | | | 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST, | | PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED | | THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE | | GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL | | NOT BE ALTERED. | | | | 2ND REVIEW, TEST SUBMITTED INCLUDES A SUSPENDED GYPSUM | | CEILING. | | | | 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART | | OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN | | DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW | | IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT | | BELOW WILL NOT BE ALTERED. | | | | 2ND REVIEW, TEST SUBMITTED INCLUDES A SUSPENDED GYPSUM | | CEILING. | | | | 3. OK |
|