Plan Review Notes
Plan Review Notes For Permit 13110381
Permit Number 13110381
Review Stop B
Sequence Number 1
Notes
Date Text
2013-11-14 07:53:202010 FBC
  
 DENIED BY BUILDING
  
 1) SPECIFY THE SQUARE FEET AREA OF THE FLAT ROOF AND
 THE SLOPED ROOF. SPECIFY THE MEAN ROOF HEIGHT AND SLOPE
 OF THE PITCHED ROOF.
  
 2) THE RAS 117 CALCULATIONS ARE FOR EXPOSURE C. THE
 STRUCTURE IS LOCATED WITHIN 600 FEET OF THE
 INTER-COASTAL WATER WAY AND IS CONSIDERED EXPOSURE D.
 FBC R301.2.1.4.3 PLEASE REVISE CALCULATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]