Plan Review Notes For Permit 13110342 |
Permit Number |
13110342 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-01-30 17:56:37 | 2010 FBC | | | | DENIED BY MECHANICAL | | | | 1) SUBMIT TWO SETS OF MECHANICAL PLANS. SPECIFY THE | | DUCT LAYOUT, SIZES, GRILL SIZES, CFMS AT EACH OUTLET, | | THE SIZE AND LOCATION OF RETURN GRILLS AND DUCTS. CITY | | AMENDMENTS 107.3.5.3 | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS. CITY | | AMENDMENTS 107.3.5.3 | | | | 3) SHOW THE LOCATION OF THE AIR HANDLER AND CONDENSER | | ON THE PLANS. CITY AMENDMENTS 107.3.5.3 | | | | 4) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED | | RETURN AIR. | | | | 5) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS | | BASED ON BUILDING LOADS CALCULATED IN ACCORDANCE WITH | | ACCA MANUAL J OR OTHER APPROVED METHODS. FBCR M1401.3 | | | | 6) THE NAME, SIGNATURE AND LICENSE NUMBER OF THE PERSON | | RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE PLANS. | | CITY AMENDMENTS 107.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|