Plan Review Notes For Permit 13110342 |
Permit Number |
13110342 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-12-30 08:53:02 | 2010 FBC | | | | DENIED BI PLUMBING | | | | 1) SHEET 7 OF THE PLANS THAT CONTAINS THE PLUMBING | | RISER IS SIGNED AND SEALED BY THE ENGINEER, HOWEVER, | | THE ENGINEER'S INFORMATION THAT IS REQUIRED BY FAC | | 61G15-23.002 TO BE IN THE TITLE BLOCK IS MISSING. | | PLEASE CORRECT. | | | | 2) BOTH OF THE TUBS ARE SHOWN CONNECTING TO A VENT | | STACK ABOVE THE ABOVE THE LAVATORIES WHICH IS NOT | | POSSIBLE UNLESS THEY WERE LOCATED ON THE FLOOR ABOVE. | | THEY SHOULD CONNECT TO THE HORIZONTAL DRAIN DOWN STREAM | | FROM THE VENT. PLEASE CORRECT. CITY AMENDMENTS 107.2.1 | | | | 3) THE MINIMUM SIZE FOR A WASHING MACHINE DRAIN IS 2" | | PER FBCR P3201.7. THE PLANS HAVE 1-1/2" PLEASE CORRECT. | | | | 4) THE MINIMUM SIZE FOR A BATHTUB IS 1-1/2" PER FBCR | | P3201.7. THE PLANS HAVE 1-1/4" PLEASE CORRECT. | | | | 5) THE STAND PIPE FOR THE CLOTHES WASHING MACHINE SHALL | | EXTEND A MINIMUM OF 18 INCHES AND A MAXIMUM OF 42 | | INCHES ABOVE THE TRAP WEIR. FBCR P2706.2 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|