Plan Review Notes For Permit 13110342 |
Permit Number |
13110342 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-12-12 17:13:23 | THE FOLLOWING ITEMS NEED TO BE ADDRESSED AND CORRECTED | | ACCORDINGLY: | | 1. REARRANGE THE OUTLET SPACING TO COMPLY WITH THE | | REQUIREMENTS OF NEC 210.52 | | 2. RELOCATE THE ELECTRICAL PANEL AS SHOWN ON THE PLANS | | TO COMPLY WITH NEC110.26. THE AREA IN FRONT OF THE | | PANEL HAS TO BE CLEAR ALL THE WAY TO THE FLOOR. | | 3. AS PER FBC-R314.3.1, SMOKE DETECTOR COMPLIANCE IS | | REQUIRED THROUGH OUT THE HOME IF NOT ALREADY IN | | COMPLIANCE. | | 4. THE LUMINAIRE IN THE ATTIC SHALL HAVE A PROTECTIVE | | GUARD AS PER NEC 410.11 | | 5. THE FLOOR PLAN LABELED "EXISTING" REFLECTS AN AHU | | WHICH APPEARS TO BE RELOCATED AS PART OF THE NEW WORK, | | INDICATE THE LOCATION OF THE "NEW" AHU AND ITS | | CORRESPONDING CU. | | 6. CORRECT THE LOAD TABLE AS SHOWN. MINIMUM OF 2 SMALL | | APPLIANCE OUTLETS ARE REQUIRED, ONLY ONE INDICATED | | 7. CORRECT THE RISER DIAGRAM TO MATCH THE LOAD TABLE | | AND PANEL SCHEDULE AS INTENDED | | 8. THE NOTE ON THE PL;ANS INDICATE THAT THE EXISTING | | SERVICE IS BEING UPGRADED TO 200AMP, PROVIDE BETTER | | DETAIL ON THIS. | | | | THIS REVIEW IS NOT INTENDED TO BE A PUNCH LIST FOR THE | | DESIGN PROFESSIONAL, THEREFORE ADDITIONAL CORRECTIONS | | MAY BE REQUIRED. A THROUGH REVIEW OF THE PROJECT BY THE | | DESIGN PROFESSIONAL IS SUGGESTED PRIOR TO THE NEXT | | SUBMITTAL | | |
|