Plan Review Notes For Permit 13110168 |
Permit Number |
13110168 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-11-08 18:34:37 | REROOF, BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- ENGINEER TO REVISE THE RAS 117 CALCULATIONS. PAGE 15 | | OF NOA 13-0129.15 SUBMITTED SHOWS BASE SHEET FASTENING | | TO BE 8"O.C. IN THE LAP AND "THREE" ADDITIONAL ROWS IN | | THE FIELD AT 8"O.C. THIS IS THE FASTENING THAT NEEDS TO | | BE USED FOR ROOF ZONE ONE AS REQUIRED BY SEC. 8.1 OF | | RAS 117. ENGINEER SPECIFIED TWO ROWS IN MID-SHEET | | INSTEAD OF THREE. THIS NEED TO BE REVISED. | | | | ***NOTE: ANY ROOF EQUIPMENT REMOVAL REQUIRES SEPARATE | | PERMIT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|