2014-01-02 11:03:50 | THE FOLLOWING ITEMS NEED TO BE ADDRESSED: | | 1. CONTROL WIRE INSULATION AS PER NEC 620.11(B) | | 2. INDICATE CONDUCTOR INSULATION AS INDICATED IN NEC | | 620.36 AS WELL AS RACEWAY TYPE FROM PANEL "1XA" TO | | PANEL "PBX" | | 3. SHOW THE PROPOSED FANS ON THE RISER DIAGRAM. | | 4. INDICATE PROPER GROUNDING AS PER NEC 620.82 OR 83 | | 5. PROVIDE ELECTRICAL DETAILS FOR "ESF1" & "ESF2" | | 6. INDICATE ALL RACEWAY TYPES AND CONDUCTOR INSULATION | | ON DRAWINGS |
|