2013-11-16 09:18:32 | BUILDING PLAN REVIEW |
| PERMIT: 13110011 |
| ADD: 250 S AUSTRALIAN AVE/ ELEVATOR SHAFT |
| PRESSURIZATION |
| CONT: CHANDLER CONSTRUCTION |
| TEL: (561)791-6934 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SAT. NOV. 16/ 2013 |
| ACTION: DENIED |
| |
| 1) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 708.14.2.2 |
| RATIONAL ANALYSIS. A RATIONAL ANALYSIS COMPLYING WITH |
| SECTION 909.4 SHALL BE SUBMITTED WITH THE CONSTRUCTION |
| DOCUMENTS. |
| |
| 2010 FBC-B 909.4 A RATIONAL ANALYSIS SUPPORTING THE |
| TYPES OF SMOKE CONTROL SYSTEMS TO BE EMPLOYED, THEIR |
| METHODS OF OPERATION, THE SYSTEMS SUPPORTING THEM AND |
| THE METHODS OF CONSTRUCTION TO BE UTILIZED SHALL |
| ACCOMPANY THE SUBMITTED CONSTRUCTION DOCUMENTS AND |
| SHALL INCLUDE, BUT NOT BE LIMITED TO, THE ITEMS |
| INDICATED IN SECTIONS 909.4.1 THROUGH 909.4.6. |
| |
| [F] 909.4.1 STACK EFFECT. |
| THE SYSTEM SHALL BE DESIGNED SUCH THAT THE MAXIMUM |
| PROBABLE NORMAL OR REVERSE STACK EFFECT WILL NOT |
| ADVERSELY INTERFERE WITH THE SYSTEM?S CAPABILITIES. IN |
| DETERMINING THE MAXIMUM PROBABLE STACK EFFECT, |
| ALTITUDE, ELEVATION, WEATHER HISTORY AND INTERIOR |
| TEMPERATURES SHALL BE USED. |
| |
| [F] 909.4.2 TEMPERATURE EFFECT OF FIRE. |
| BUOYANCY AND EXPANSION CAUSED BY THE DESIGN FIRE IN |
| ACCORDANCE WITH SECTION 909.9 SHALL BE ANALYZED. THE |
| SYSTEM SHALL BE DESIGNED SUCH THAT THESE EFFECTS DO NOT |
| ADVERSELY INTERFERE WITH THE SYSTEM?S CAPABILITIES. |
| |
| [F] 909.4.3 WIND EFFECT. |
| THE DESIGN SHALL CONSIDER THE ADVERSE EFFECTS OF WIND. |
| SUCH CONSIDERATION SHALL BE CONSISTENT WITH THE |
| WIND-LOADING PROVISIONS OF CHAPTER 16. |
| |
| [F] 909.4.4 HVAC SYSTEMS. |
| THE DESIGN SHALL CONSIDER THE EFFECTS OF THE HEATING, |
| VENTILATING AND AIR-CONDITIONING (HVAC) SYSTEMS ON BOTH |
| SMOKE AND FIRE TRANSPORT. THE ANALYSIS SHALL INCLUDE |
| ALL PERMUTATIONS OF SYSTEMS STATUS. THE DESIGN SHALL |
| CONSIDER THE EFFECTS OF THE FIRE ON THE HVAC SYSTEMS. |
| |
| [F] 909.4.5 CLIMATE. |
| THE DESIGN SHALL CONSIDER THE EFFECTS OF LOW |
| TEMPERATURES ON SYSTEMS, PROPERTY AND OCCUPANTS. AIR |
| INLETS AND EXHAUSTS SHALL BE LOCATED SO AS TO PREVENT |
| SNOW OR ICE BLOCKAGE. |
| |
| [F] 909.4.6 DURATION OF OPERATION. |
| ALL PORTIONS OF ACTIVE OR PASSIVE SMOKE CONTROL SYSTEMS |
| SHALL BE CAPABLE OF CONTINUED OPERATION AFTER DETECTION |
| OF THE FIRE EVENT FOR A PERIOD OF NOT LESS THAN EITHER |
| 20 MINUTES OR 1.5 TIMES THE CALCULATED EGRESS TIME, |
| WHICHEVER IS LESS. |
| |
| 2) SHEET M5.1 INDICATES THE ELEVATOR LEAKAGE CALULATION |
| TO BE 300 300 CFM PER DOOR. 707.14.2.3.4 FAN CAPACITY |
| INDICATES THE ADJUSTABLE FAN BE ABLE TO MEET 1,000 CFM |
| OR THE DESIGN PROFESSIONAL CAN DESIGN THE SYSTEM TO |
| OPERATE IN THE RANGE OF 0.04 TO 0.06 INCHES OF WATER |
| COLUMN SPECIFIED IN THE PRESSURE REQUIREMENTS OF |
| SECTION 708.14.2.1. PLEASE PROVIDE THE CALCULATION |
| PORTION FOR THE REQUIRED 0.04 TO 0.06 WATER COLUMN. |
| |
| |
| 3) 708.14.2.8 MARKING AND IDENTIFICATION. DETECTION AND |
| CONTROL SYSTEMS SHALL BE MARKED IN ACCORDANCE WITH |
| SECTION 909.14. |
| [F] 909.14 MARKING AND IDENTIFICATION. |
| THE DETECTION AND CONTROL SYSTEMS SHALL BE CLEARLY |
| MARKED AT ALL JUNCTIONS, ACCESSES AND TERMINATIONS. |
| |
| 4) 708.14.2.9 CONTROL DIAGRAMS. CONTROL DIAGRAMS SHALL |
| BE PROVIDED IN ACCORDANCE WITH SECTION 909.15. |
| [F] 909.15 CONTROL DIAGRAMS. |
| IDENTICAL CONTROL DIAGRAMS SHOWING ALL DEVICES IN THE |
| SYSTEM AND IDENTIFYING THEIR LOCATION AND FUNCTION |
| SHALL BE MAINTAINED CURRENT AND KEPT ON FILE WITH THE |
| BUILDING OFFICIAL, THE FIRE DEPARTMENT AND IN THE FIRE |
| COMMAND CENTER IN A FORMAT AND MANNER APPROVED BY THE |
| FIRE CHIEF. |
| |
| 5) 708.14.2.10 CONTROL PANEL. A CONTROL PANEL COMPLYING |
| WITH SECTION 909.16 SHALL BE PROVIDED. |
| [F] 909.16 FIRE-FIGHTER?S SMOKE CONTROL PANEL. |
| A FIRE-FIGHTER?S SMOKE CONTROL PANEL FOR FIRE |
| DEPARTMENT EMERGENCY RESPONSE PURPOSES ONLY SHALL BE |
| PROVIDED AND SHALL INCLUDE MANUAL CONTROL OR OVERRIDE |
| OF AUTOMATIC CONTROL FOR MECHANICAL SMOKE CONTROL |
| SYSTEMS. THE PANEL SHALL BE LOCATED IN A FIRE COMMAND |
| CENTER COMPLYING WITH SECTION 911 IN HIGHRISE BUILDINGS |
| OR BUILDINGS WITH SMOKE-PROTECTED ASSEMBLY SEATING. IN |
| ALL OTHER BUILDINGS, THE FIRE-FIGHTER?S SMOKE CONTROL |
| PANEL SHALL BE INSTALLED IN AN APPROVED LOCATION |
| ADJACENT TO THE FIRE ALARM CONTROL PANEL. THE |
| FIRE-FIGHTER?S SMOKE CONTROL PANEL SHALL COMPLY WITH |
| SECTIONS 909.16.1 THROUGH 909.16.3. |
| |
| [F] 909.16.1 SMOKE CONTROL SYSTEMS. |
| FANS WITHIN THE BUILDING SHALL BE SHOWN ON THE |
| FIRE-FIGHTER?S CONTROL PANEL. A CLEAR INDICATION OF THE |
| DIRECTION OF AIRFLOW AND THE RELATIONSHIP OF COMPONENTS |
| SHALL BE DISPLAYED. STATUS INDICATORS SHALL BE PROVIDED |
| FOR ALL SMOKE CONTROL EQUIPMENT, ANNUNCIATED BY FAN AND |
| ZONE, AND BY PILOT-LAMP-TYPE INDICATORS AS FOLLOWS: |
| 1. FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN THEIR |
| NORMAL STATUS?WHITE. |
| 2. FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN THEIR |
| OFF OR CLOSED STATUS?RED. |
| 3. FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN THEIR |
| ON OR OPEN STATUS?GREEN. |
| 4. FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN A |
| FAULT STATUS?YELLOW/AMBER. |
| |
| [F] 909.16.2 SMOKE CONTROL PANEL. |
| THE FIRE-FIGHTER?S CONTROL PANEL SHALL PROVIDE CONTROL |
| CAPABILITY OVER THE COMPLETE SMOKE-CONTROL SYSTEM |
| EQUIPMENT WITHIN THE BUILDING AS FOLLOWS: |
| 1. ON-AUTO-OFF CONTROL OVER EACH INDIVIDUAL PIECE OF |
| OPERATING SMOKE CONTROL EQUIPMENT THAT CAN ALSO BE |
| CONTROLLED FROM OTHER SOURCES WITHIN THE BUILDING. THIS |
| INCLUDES STAIRWAY PRESSURIZATION FANS; SMOKE EXHAUST |
| FANS; SUPPLY, RETURN AND EXHAUST FANS; ELEVATOR SHAFT |
| FANS AND OTHER OPERATING EQUIPMENT USED OR INTENDED FOR |
| SMOKE CONTROL PURPOSES. |
| 2. OPEN-AUTO-CLOSE CONTROL OVER INDIVIDUAL DAMPERS |
| RELATING TO SMOKE CONTROL AND THAT ARE ALSO CONTROLLED |
| FROM OTHER SOURCES WITHIN THE BUILDING. |
| 3. ON-OFF OR OPEN-CLOSE CONTROL OVER SMOKE CONTROL AND |
| OTHER CRITICAL EQUIPMENT ASSOCIATED WITH A FIRE OR |
| SMOKE EMERGENCY AND THAT CAN ONLY BE CONTROLLED FROM |
| THE FIRE-FIGHTER?S CONTROL PANEL. |
| EXCEPTIONS: |
| 1. COMPLEX SYSTEMS, WHERE APPROVED, WHERE THE CONTROLS |
| AND INDICATORS ARE COMBINED TO CONTROL AND INDICATE ALL |
| ELEMENTS OF A SINGLE SMOKE ZONE AS A UNIT. |
| 2. COMPLEX SYSTEMS, WHERE APPROVED, WHERE THE CONTROL |
| IS ACCOMPLISHED BY COMPUTER INTERFACE USING APPROVED, |
| PLAIN ENGLISH COMMANDS. |
| |
| 6) 708.14.2.11 SYSTEM RESPONSE TIME. HOISTWAY |
| PRESSURIZATION SYSTEMS SHALL COMPLY WITH THE |
| REQUIREMENTS FOR SMOKE CONTROL SYSTEM RESPONSE TIME IN |
| SECTION 909.17. |
| [F] 909.17 SYSTEM RESPONSE TIME. |
| SMOKE-CONTROL SYSTEM ACTIVATION SHALL BE INITIATED |
| IMMEDIATELY AFTER RECEIPT OF AN APPROPRIATE AUTOMATIC |
| OR MANUAL ACTIVATION COMMAND. SMOKE CONTROL SYSTEMS |
| SHALL ACTIVATE INDIVIDUAL COMPONENTS (SUCH AS DAMPERS |
| AND FANS) IN THE SEQUENCE NECESSARY TO PREVENT PHYSICAL |
| DAMAGE TO THE FANS, DAMPERS, DUCTS AND OTHER EQUIPMENT. |
| FOR PURPOSES OF SMOKE CONTROL, THE FIRE-FIGHTER?S |
| CONTROL PANEL RESPONSE TIME SHALL BE THE SAME FOR |
| AUTOMATIC OR MANUAL SMOKE CONTROL ACTION INITIATED FROM |
| ANY OTHER BUILDING CONTROL POINT. THE TOTAL RESPONSE |
| TIME, INCLUDING THAT NECESSARY FOR DETECTION, SHUTDOWN |
| OF OPERATING EQUIPMENT AND SMOKE CONTROL SYSTEM |
| STARTUP, SHALL ALLOW FOR FULL OPERATIONAL MODE TO BE |
| ACHIEVED BEFORE THE CONDITIONS IN THE SPACE EXCEED THE |
| DESIGN SMOKE CONDITION. THE SYSTEM RESPONSE TIME FOR |
| EACH COMPONENT AND THEIR SEQUENTIAL RELATIONSHIPS SHALL |
| BE DETAILED IN THE REQUIRED RATIONAL ANALYSIS AND |
| VERIFICATION OF THEIR INSTALLED CONDITION REPORTED IN |
| THE REQUIRED FINAL REPORT. |
| |