Notes
Date Text
2013-11-01 06:57:262010 FBC
  
 DENIED BY BUILDING
  
 1) THE DESIGN PRESSURES FOR THE PROPOSED SYSTEM ON PAGE
 6 OF NOA NO. 12-0221.02 FOR THE TARCO SELF-ADHERED
 ROOFING SYSTEM HAS A MAXIMUM DESIGN PRESSURE OF -60
 PSF. THE TWO STORY STRUCTURE IS LOCATED IN A 170 MPH
 VULT WIND SPEED AND EXPOSURE CATEGORY C. THE PERIMETER
 AND CORNER AREAS WILL REQUIRE ENHANCED FASTENING.
 SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY LIMITATION NUMBER 7 ON PAGE
 7 OF THE NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]