Plan Review Notes For Permit 13101141 |
Permit Number |
13101141 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-11-01 06:57:26 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE DESIGN PRESSURES FOR THE PROPOSED SYSTEM ON PAGE | | 6 OF NOA NO. 12-0221.02 FOR THE TARCO SELF-ADHERED | | ROOFING SYSTEM HAS A MAXIMUM DESIGN PRESSURE OF -60 | | PSF. THE TWO STORY STRUCTURE IS LOCATED IN A 170 MPH | | VULT WIND SPEED AND EXPOSURE CATEGORY C. THE PERIMETER | | AND CORNER AREAS WILL REQUIRE ENHANCED FASTENING. | | SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 | | CALCULATIONS AS REQUIRED BY LIMITATION NUMBER 7 ON PAGE | | 7 OF THE NOA. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|