2013-12-04 18:29:22 | 2010 FBC | | | | DENIED BY MECHANICAL | | | | 1) A MECHANICAL PERMIT IS REQUIRED TO REPLACE THE HVAC | | EQUIPMENT AS NOTED IN THE CITY'S WORK SPECIFICATIONS. | | CITY AMENDMENTS 105.1 | | | | 2) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS | | AS SPECIFIED IN THE SCOPE OF WORK. FBCR M1401.3 | | | | 3) SUBMIT TWO SETS OF MECHANICAL PLANS SHOWING THE | | LOCATION OF THE EQUIPMENT, THE SUPPLY DUCT SIZE, | | LOCATION, GRILL SIZES, CFMS AT EACH SUPPLY OUTLET AND | | THE RETURN DUCT SIZE, LOCATION, GRILL SIZES. CITY | | AMENDMENTS 107.3.5.3 | | | | 4) SHOW COMPLIANCE WITH BALANCED RETURN AIR AS REQUIRED | | BY FBCR M1602.4. | | | | 5) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT IS | | CONSISTENT WITH THE SIZING CALCULATIONS. THE NAME AN | | LICENSE NUMBER OF THE PERSON RESPONSIBLE FOR THE DESIGN | | IS REQUIRED ON THE MECHANICAL PLANS. CITY AMENDMENTS | | 107.2.1.3 AND FS 471.003 (2) (H) | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|