Plan Review Notes
Plan Review Notes For Permit 13101138
Permit Number 13101138
Review Stop M
Sequence Number 1
Notes
Date Text
2013-12-04 18:29:222010 FBC
  
 DENIED BY MECHANICAL
  
 1) A MECHANICAL PERMIT IS REQUIRED TO REPLACE THE HVAC
 EQUIPMENT AS NOTED IN THE CITY'S WORK SPECIFICATIONS.
 CITY AMENDMENTS 105.1
  
 2) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS
 AS SPECIFIED IN THE SCOPE OF WORK. FBCR M1401.3
  
 3) SUBMIT TWO SETS OF MECHANICAL PLANS SHOWING THE
 LOCATION OF THE EQUIPMENT, THE SUPPLY DUCT SIZE,
 LOCATION, GRILL SIZES, CFMS AT EACH SUPPLY OUTLET AND
 THE RETURN DUCT SIZE, LOCATION, GRILL SIZES. CITY
 AMENDMENTS 107.3.5.3
  
 4) SHOW COMPLIANCE WITH BALANCED RETURN AIR AS REQUIRED
 BY FBCR M1602.4.
  
 5) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT IS
 CONSISTENT WITH THE SIZING CALCULATIONS. THE NAME AN
 LICENSE NUMBER OF THE PERSON RESPONSIBLE FOR THE DESIGN
 IS REQUIRED ON THE MECHANICAL PLANS. CITY AMENDMENTS
 107.2.1.3 AND FS 471.003 (2) (H)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]