2013-12-04 18:58:302010 FBC / 2008 NEC
  
 DENIED BY ELECTRICAL
  
 1) SUBMIT TWO SETS OF LOAD CALCULATIONS FOR THE
 DWELLING UNIT INCLUDING ALL OF THE NEW ELECTRICAL
 EQUIPMENT. CITY AMENDMENTS 107.3.5.3
  
 2) SUBMIT TWO COPIES OF A PANEL SCHEDULE FOR THE
 EXISTING SERVICE INCLUDING ALL NEW AND UPGRADED
 CIRCUITS. CITY AMENDMENTS 107.3.5.3
  
 3) SUBMIT THE SPECIFICATIONS WITH THE ELECTRICAL
 REQUIREMENTS FOR THE NEW TANKLESS ELECTRIC WATER
 HEATER. NEC 110.3(B)
  
 4) THE SMOKE ALARMS ARE TO BE LOCATED IN THE SLEEPING
 ROOMS SO THAT THEY WILL PROVIDE THE MOST EFFECTIVE
 COVERAGE IN ACCORDANCE WITH THEIR LISTING/LABELING. NEC
 110.3(B)
  
 5) THE NAME AND LICENSE NUMBER OF THE PERSON
 RESPONSIBLE FOR THE DESIGN IS REQUIRED TO BE ON THE
 ELECTRICAL DRAWINGS. FS 471.003(2)(H)
  