2013-10-28 14:40:17 | PERMIT #13100950 | | MASTER # 13070818 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION. | | | | PLANS DO NOT SHOW LOCATION(S) OF EMERGENCY PULL | | STATION(S). PER FBC 904.11.1, A MANUAL ACTIVATION | | DEVICE SHALL BE LOCATED ALONG THE EGRESS PATH AND BE A | | MINIMUM OF 10 FEET AND A MAXIMUM OF 20 FEET FROM THE | | KITCHEN EXHAUST SYSTEM. THE DEVICE SHALL BE MOUNTED | | 42-48 INCHES ABOVE THE FLOOR AND SHALL CLEARLY IDENTIFY | | THE HAZARD PROTECTED. | | | | KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE | | BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL FIRE | | ALARM CONDITION. | | | | SUE ELLEN CALDERON | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 804-4751 | | |
|