2013-10-28 14:40:17PERMIT #13100950
 MASTER # 13070818
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 PLANS DO NOT SHOW LOCATION(S) OF EMERGENCY PULL
 STATION(S). PER FBC 904.11.1, A MANUAL ACTIVATION
 DEVICE SHALL BE LOCATED ALONG THE EGRESS PATH AND BE A
 MINIMUM OF 10 FEET AND A MAXIMUM OF 20 FEET FROM THE
 KITCHEN EXHAUST SYSTEM. THE DEVICE SHALL BE MOUNTED
 42-48 INCHES ABOVE THE FLOOR AND SHALL CLEARLY IDENTIFY
 THE HAZARD PROTECTED.
  
 KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE
 BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL FIRE
 ALARM CONDITION.
  