2013-11-06 14:32:30313 DATURA STREET
 PERMIT #13100881
 MASTER #13050713
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL
 - PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 - FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN
 APPROVED SUPERVISING STATION IN ACCORDANCE WITH NFPA
 72.
  
 - SPRINKLER PROTECTION WILL BE REQUIRED ON THE FIRST
 AND SECOND FLOOR OF THE ENCLOSED STAIR BECAUSE THE
 STAIR SHAFT IS DISCONTINUOUS TO THE THIRD FLOOR.
  
 1ST FLOOR
 - PROVIDE SPRINKLER PROTECTION BELOW STAIR #1 IF
 PROTECTION DOES NOT ALREADY EXIST.
  
 - SPRINKLER BRANCH LINES ARE PERMITTED TO SUPPLY
 SPRINKLERS IN ELECTRICAL ROOMS; HOWEVER, BRACHLINES
 SHALL NOT BE ROUTED THROUGH (IN AND OUT) ELECTRICAL
 ROOMS. SEE ELECTRICAL ROOM #109 & #114.
  
 2ND FLOOR
 - PROVIDE SPRINKLER PROTECTION IN ELEVATOR MACHINE ROOM
 #216.
  
 NOTE: SPRINKLERS IN STOARGE SPACE #100 INDICATED AS
 "NOT IN CONTRACT" NIC -
 PER NFPA 25 SECTION 5.3.1.1.1, WHERE SPRINKLERS HAVE
 BEEN IN SERVICE FOR 50 YEARS, THEY SHALL BE REPLACED OR
 REPRESENTATIVE SAMPLES FROM ONE OR MORE SAMPLE AREAS
 SHALL BE TESTED. TEST PROCEDURES SHALL BE REPEATED AT
 10-YEAR INTERVALS. WHERE REQUIRED BY THIS SECTION,
 SAMPLE SPRINKLERS SHALL BE SUBMITTED TO A RECOGNIZED
 TESTING LABORATORY ACCEPTABLE TO THE AUTHORITY HAVING
 JURISDICTION FOR FIELD SERVICE TESTING.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  