| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| GENERAL |
| - PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT |
| CONNECTION. |
| |
| - FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN |
| APPROVED SUPERVISING STATION IN ACCORDANCE WITH NFPA |
| 72. |
| |
| - SPRINKLER PROTECTION WILL BE REQUIRED ON THE FIRST |
| AND SECOND FLOOR OF THE ENCLOSED STAIR BECAUSE THE |
| STAIR SHAFT IS DISCONTINUOUS TO THE THIRD FLOOR. |
| |
| 1ST FLOOR |
| - PROVIDE SPRINKLER PROTECTION BELOW STAIR #1 IF |
| PROTECTION DOES NOT ALREADY EXIST. |
| |
| - SPRINKLER BRANCH LINES ARE PERMITTED TO SUPPLY |
| SPRINKLERS IN ELECTRICAL ROOMS; HOWEVER, BRACHLINES |
| SHALL NOT BE ROUTED THROUGH (IN AND OUT) ELECTRICAL |
| ROOMS. SEE ELECTRICAL ROOM #109 & #114. |
| |
| 2ND FLOOR |
| - PROVIDE SPRINKLER PROTECTION IN ELEVATOR MACHINE ROOM |
| #216. |
| |
| NOTE: SPRINKLERS IN STOARGE SPACE #100 INDICATED AS |
| "NOT IN CONTRACT" NIC - |
| PER NFPA 25 SECTION 5.3.1.1.1, WHERE SPRINKLERS HAVE |
| BEEN IN SERVICE FOR 50 YEARS, THEY SHALL BE REPLACED OR |
| REPRESENTATIVE SAMPLES FROM ONE OR MORE SAMPLE AREAS |
| SHALL BE TESTED. TEST PROCEDURES SHALL BE REPEATED AT |
| 10-YEAR INTERVALS. WHERE REQUIRED BY THIS SECTION, |
| SAMPLE SPRINKLERS SHALL BE SUBMITTED TO A RECOGNIZED |
| TESTING LABORATORY ACCEPTABLE TO THE AUTHORITY HAVING |
| JURISDICTION FOR FIELD SERVICE TESTING. |
| |