Plan Review Notes For Permit 13100771 |
Permit Number |
13100771 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-10-22 19:02:53 | AS PER NEC 310 #6 WIRE IS NOT RATED FOR 100 AMP. | | CORRECT YOUR RISER DIAGRAM ACCORDINGLY AND RESUBMIT FOR | | APPROVAL. | | | | SENT TO SH DESK |
|