Plan Review Notes For Permit 13100771
Permit Number 13100771
Review Stop E
Sequence Number 1
Notes
Date Text
2013-10-22 19:02:53AS PER NEC 310 #6 WIRE IS NOT RATED FOR 100 AMP.
 CORRECT YOUR RISER DIAGRAM ACCORDINGLY AND RESUBMIT FOR
 APPROVAL.
  
 SENT TO SH DESK